Operation
5. Maintenance report
The maintenance report displays all smoke sensors
on the
specified loop or loops detected as
dirty (
% alarm > 75
). The percent of alarm rises as the detector gets dirty. A trouble occurs
once the percentage reaches 75%. The report shows the device address, percentage dirty,
device type, and programmed message in the following format:
Enter the loop number of the desired device and press the
Enter
button.
The maintenance report is shown in the following format.
The user can press
UP
and
DOWN
cursor key to scroll through all the devices on the loop for
which the maintenance report is available. If there are no dirty devices on the loop the
following message will be displayed
6. A/P Report
The Advanced Protocol (AP) Report will display or list on a printer all local parameters of an
AP device currently connected on the SLC. This feature will list the internal register values of
current AP devices. Since parameter values and addresses are not disclosed to the user, this
tool is used to report information to Mircom technical support.
If the panel is connected to a printer the user will be prompted to select an output source:
If “Printer” is selected the user will be prompted to select the address range. “All” selects all
addresses from all configured loops and “Loop” selects addresses from one loop.
If “Loop” is selected the user will be prompted to enter a loop number:
If the panel does not have a printer connected or if the user selects “Screen” under the report
to menu only one address will be displayed. The user will be prompted to enter this address:
Once the report is on display it will list all the parameters of all the subaddresses related to the
device. In this display “Crt.” indicates report line number, “S/A” indicates device current
Loop Number
Loop :__
Maint Report
Percent dirty :012%
No dirty devices
found
- Report To -
1. Printer
2. Screen
1. All
2. Loop
Loop Number
Loop: _
Device Address
Loop: _ Devaddr:___