Installation and Operation Manual
57
Polarity Reversal and City Tie Module (PR-300) Wiring
Wire PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 42 below. Power Limited cable type
FPL, FPLR or FPLP must be used.
For USA installation, the installer must use
Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective
Device
, or similar
UL-Listed QVRG secondary protector
, as shown.
For use in Canada, the Protective Device is not required but still recommended.
Figure 42: Polarity reversal and city tie module terminal connection
Notes:
• Either the PR-300's city tie or polarity reversal interface may be used, but not both.
• The city tie interface is not power limited.
• Plug PR-300 ribbon cable (P1) into connector (P4) of the FX-2000N main fire alarm module.
• Cut jumper (JW1) on the PR-300 module in order to transmit a trouble condition to the monitoring station.
• Remove jumper plug from jumper JW4 on the main fire alarm module.
• The polarity reversal interface is power limited and must use type FPL, FPLR, or FPLP power limited
cable.
• For polarity reversal operation, short the city tie connection.
1
1
2
2
S
S
CITY TIE LOCAL ENERGY
POLARITY REVERSAL ALARM
POLARITY REVERSAL SUPV.
PROTECTOR
1
1
2
2
S
S
1
1
2
2
S
S
1
1
2
2
S
S
+
+
+
-
-
-
+
+
+
-
-
-
DIN RAIL CONNECTION
TO EARTH GROUND
DIN RAIL CONNECTION
TO EARTH GROUND
POWER LIMITED
POWER LIMITED
PR-300
POWER LIMITED CABLE TYPE
FPL
,
FPLR
or
FPLP
MUST BE USED
FROM PR-300 TO PROTECTORS.
PROTECTOR
PROTECTOR
PR
O
T
E
C
T
E
D
PR
O
T
E
C
T
E
D
UNP
RO
T
E
C
T
ED
UNP
RO
T
E
C
T
ED
RATED - 24VDC FILTERED
TRIP COIL - 14 Ohms, 250mA
5mV RIPPLE
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
CONFORMS TO NEMA
STANDARD 2011 INTENDED
FOR CONNECTION TO
POLARITY REVERSAL CIRCUIT
OF A REMOTE STATION
RECEIVING UNIT HAVING
COMPATIBLE RATINGS
USE A SHORTING WIRE WHEN
THE CITY TIE IS NOT USED