7. SYSTEM CHECKOUT
BEFORE TURNING POWER ON:
1. Check all external wiring for opens, shorts or grounds.
2. Check that transformer cables are securely connected.
3. Check the
A.C.
power wiring for proper connection.
DO NOT
connect batteries in order to
prevent sparking.
4. Check that all switches are in the normal position to the left.
8. POWER UP AND TROUBLESHOOTING
1. After completing all of the system checkout procedures, power up the panel. The
A.C. On
LED
should illuminate.
2. The
trouble
buzzer should sound intermittently, the
common trouble
LED flash, indicating
battery fault.
3. Connect the batteries carefully, observing the correct polarity.
4. The
common trouble
LED should extinguish. If the
common trouble
LED stays
on
, check the
front panel for the illumination of the following LEDs;
a) BATTERY LED - battery voltage may be too low, below 20.4V.
b) GROUND FAULT LED - indicates a ground on one or more of the extended wires.
c) ZONE TROUBLE LED - indicates an open loop or a
signal silence
switch is in the
off
normal position to the right.
d) SIGNAL TROUBLE LED - indicates an open loop or short in the signal zone.
Содержание FA-101U
Страница 7: ... 5 FIGURE 1 BACKBOX FLUSH TRIM MOUNTING DETAILS ...
Страница 8: ... 6 FIGURE 2 CIRCUIT BOARD LAYOUT ...
Страница 9: ... 7 FIGURE 3 DETECTION AND SIGNAL WIRING INSTRUCTION ...
Страница 10: ... 8 FIGURE 4 WIRING TABLE FOR DETECTION ZONE ...
Страница 11: ... 9 FIGURE 5 WIRING TABLE FOR BELLS AND HORNS ...
Страница 12: ... 10 FIGURE 6 ALARM AND TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS ...
Страница 17: ......
Страница 18: ...Notes ...
Страница 19: ......