UNDERWRITER’S LABS INC. (ULI)
UNITED STATES 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY
NOTES:
1. Reset time, hold for five seconds minimum.
2. Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit,
total standby current of all detectors must not exceed 3 mA.
3. The below listed Smoke Detectors are compatible with Initiating Circuits having Compatability Identifier "A".
SMOKE DETECTOR
COMPATIBILITY
RATED STANDBY
SMOKE DETECTOR
COMPATIBILITY
RATED STANDBY
MAKE MODEL /
IDENTIFIER
CURRENT
MAKE MODEL /
IDENTIFIER
CURRENT
BASE
HEAD / BASE
BASE
HEAD / BASE
SYSTEM SENSOR
SENTROL - ESL
1100
A - N/A
0.12 mA
429C
S10A - N/A
0.10 mA
1151 / B110LP
A - A
0.12 mA
429CT
S10A - N/A
0.10 mA
1151 / B116LP
A - A
0.12 mA
429CST
S11A - N/A
0.10 mA
1400
A - N/A
0.10 mA
429CRT
S11A - N/A
0.10 mA
1451 / B401
A - A
0.12 mA
711U / 701E, 701U,
S10A - S00
0.10 mA
702E, 702U
1451 / B401B
A - A
0.12 mA
712U / 701E, 701U,
S10A - S00
0.10 mA
702E, 702U
1451 / B406B
A - A
0.12 mA
713-5U / 701E,
S10A - S00
0.10 mA
701U, 702E, 702U
1451DH / DH400
A - A
0.12 mA
713-6U / 701E,
S10A - S00
0.10 mA
701U, 702E, 702U
2100
A - N/A
0.12 mA
721U / 702E, 702U
S10A - S00
0.10 mA
2100T
A - N/A
0.12 mA
721UT / 702E, 702U
S10A - S00
0.10 mA
2151 / B110LP
A - A
0.12 mA
722U / 702E, 702U
S10A - S00
0.10 mA
2151 / B116LP
A - A
0.12 mA
731U / 702E, 702U,
S11A - S00
0.10 mA
702RE, 702RU
2400
A - N/A
0.12 mA
732U / 702E, 702U,
S11A - S00
0.10 mA
702RE, 702RU
2400TH
A - N/A
0.12 mA
2400AT
A - N/A
0.12 mA
DETECTION
SYSTEMS INC.
2400AIT
A - N/A
0.12 mA
DS250
B - N/A
0.10 mA
2451 / B401B
A - A
0.12 mA
DS250TH
B - N/A
0.10 mA
2451 / B406B
A - A
0.12 mA
DS282
B - N/A
0.10 mA
2451 / DH400
A - N/A
0.12 mA
DS282TH
B - N/A
0.10 mA
2451TH / B401B
A - A
0.12 mA
2451TH / B406B
A - A
0.12 mA
2451 / B401
A - A
0.12 mA
2451TH / B401
A - A
0.12 mA
4451HT / B401B
A - A
0.12 mA
4451HT / B406B
A - A
0.12 mA
MIRCOM
4451HT / B401
A - A
0.12 mA
MIR-525U
FDT-1
0.10 mA
5451 / B401B
A - A
0.12 mA
MIR-525TU
FDT-1
0.10 mA
5451 / B401
A - A
0.12 mA
5451 / B406B
A - A
0.12 mA
Содержание FA-101U
Страница 7: ... 5 FIGURE 1 BACKBOX FLUSH TRIM MOUNTING DETAILS ...
Страница 8: ... 6 FIGURE 2 CIRCUIT BOARD LAYOUT ...
Страница 9: ... 7 FIGURE 3 DETECTION AND SIGNAL WIRING INSTRUCTION ...
Страница 10: ... 8 FIGURE 4 WIRING TABLE FOR DETECTION ZONE ...
Страница 11: ... 9 FIGURE 5 WIRING TABLE FOR BELLS AND HORNS ...
Страница 12: ... 10 FIGURE 6 ALARM AND TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS ...
Страница 17: ......
Страница 18: ...Notes ...
Страница 19: ......