Page 5

POWER UP PROCEDURES

1.  Unplug Fire Alarm Panel.

2.  Connect cable from P2 on the DACT-100A board to the Fire Alarm Panel.  Check the Fire Alarm manual for the
DACT-100A cable location.

3.  Hook up the CFG-100 Configuration Tool to P4 on the DACT-100A. 

4.  Hook up the telephone lines and telephone as shown on page 4.  

For test purposes only

 you may tie the output of telephone line 1 into the input of telephone line 2.

5.  Power up the Fire alarm and the message of the CFG-100 Configuration Tool should be:

Digital Communicator

[DACT is idle. . .]

Press any key to start login procedure . . .

6.  Press any key to start the login procedure.  The CFG-100 display will show the following screen:

Enter Passcode now

Passcode: _ _ _ _ _ _ _ _

Press <#> when done
     or  <*>  to cancel.

7.  Enter the passcode, 2222222 for installer.

Enter 2-digit ITEM
number to configure.
To scroll down list of items, press <#> or <*> to scroll up . . .

8.  When you try to enter a 2-digit number, the following screen will appear,

Please enter ITEM #

ITEM Number: _ _

Press <#> when done
      or <*>  to cancel.

9.  Set the DATE by entering 20, the following screens will appear,

Enter Date (dd/mm/yy)

Enter Date (dd/mm/yy)

Enter Date (dd/mm/yy)

Day of Month: _ _

Month of Year: _ _

Year of Century: _ _

Press <#> when done

Press <#> when done

Press <#> when done

      or <*>  to cancel.

or <*>  to cancel.

or <*>  to cancel.

10.  Set the TIME by entering 21(Item number), the following screens will appear,

Enter Time (HH/MM/SS)

Enter Time (HH/MM/SS)

Time (HH/MM/SS)

 

Seconds (00-59): _ _

Minutes (00-59): _ _

Hours (00-23): _ _

Press <#> when done

Press <#> when done

Press <#> when done

      or <*>  to cancel.

or <*>  to cancel.

or <*>  to cancel.

11.  Enter 30 and then the monitoring station account numbers and telephone numbers of the telephone lines
being used.  The following screens for telephone Line 1 will appear,

Содержание DACT-100A

Страница 1: ...pecifications contained in this manual are subject to change without prior notice by the manufacturer DACT 100A Digital Communicator INSTALLATION and OPERATION MANUAL 2005 by Mircom Technologies Limit...

Страница 2: ...n the U S A Page 2 CONNECTIONS AND SETTINGS Page 3 FIELD WIRING Page 4 POWER UP PROCEDURES Page 5 SYSTEM CONFIGURATION OPERATION Page 7 REPORTING FORMATS Page 9 COMPATIBLE FIRE ALARM CONTROL PANELS Pa...

Страница 3: ...ols T The DACT 100A can transmit Common Alarm Common Supervisory and Common Trouble information on two telephone lines The DACT Products continuously supervise the state of each of two connected Telco...

Страница 4: ...d Fire Alarm Control Panel under Standard 864 Control Units for Fire Protective Signalling Systems These Communicators complywith the National Fire Protection Association NFPA performance requirements...

Страница 5: ...m Control Panel FACP P2 RS 485 Connection for future expansion P4 Connector for CFG 100 Configuration Module I2 Status Indicator LED for Telco Line 1 Red when the line is in use Amber when there is a...

Страница 6: ...one on the first Telephone Line via the required RJ31X Connector Line 2 Input Tip Ring To the second Telephone Line via the required RJ31X Connector Line 3 Output Tip Ring To an optional Premise Telep...

Страница 7: ...de 2222222 for installer Enter 2 digit ITEM number to configure To scroll down list of items press or to scroll up 8 When you try to enter a 2 digit number the following screen will appear Please ente...

Страница 8: ...Contact ID Format is _ Format is _ Press when done Press when done or to cancel or to cancel 13 Enter 11 to initiate the test report the screen will go through the following sequences Digital Communic...

Страница 9: ...ator Reporting event Date Time The next screen is Digital Communicator Waiting for KISS Date Time If the screen stays in the Waiting for KISS mode then you should contact our Tech Support otherwise wh...

Страница 10: ...associated with individual level I OPERATOR and II INSTALLER 10 I II Event Logging Flush all events Terminate any in progress event reporting Remove report pending trigger i e cancel attempts to repor...

Страница 11: ...nt 1 Choose which Account 1 or 2 will be the first to be attempted to be reached by the DACT when a TROUBLE event is to be reported See ITEM 50 for a description of the DACT report attempt operation 5...

Страница 12: ...Trouble New event 1 300 00 000 System Trouble restored Trouble Restore 3 300 00 000 Supervisory condition Supervisory New event 1 200 00 000 Supervisory restored Supervisory Restore 3 200 00 000 SECUR...

Страница 13: ...roved SIA DCS and Ademco Contact ID Radionics Model D6500 Receiver ULI Approved Ademco Contact ID Radionics Model D6600 Receiver ULI Approved SIA DCS and Ademco Contact ID All Circuits are Power Limit...

Страница 14: ...If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage...

Страница 15: ...appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not...

Страница 16: ...llation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any other abuse...

Страница 17: ...ged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not limited to c...

Страница 18: ...area code ____________________ Reporting Format 9 Contact ID 9 SIA _________________________________________________________________________________________ Account 2 Identification max 6 digits _ _...

Страница 19: ......

Страница 20: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2006 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Отзывы: