background image

39

Error

Error Code

Error

Error 

Code

Return air temperature sensor open/

short circuited

F1

Drive board communication error

P6

Evaporator temperature sensor open/

short circuited

F2

Compressor overheating protection

H3

Indoor unit liquid valve temperature 

sensor open/short ciruited

b5

Indoor and Outdoor units unmatched

LP

Indoor gas valve temperature sensor 

open/short circuited

b7

Communication line misconnected or 

expansion valve error

dn

IPM temperature sensor open/short 

circuited

P7

Running mode conflict

E7

Outdoor ambient temperature sensor 

open/short circuited

F3

Pump-down

Fo

Outdoor unit condenser mid-tube tem-

perature sensor open/short circuited

F4

Jumper error

C5

Discharge temperature sensor open/

short circuited

F5

Forced defrosting

H1

Indoor and outdoor communication error

E6

Compressor startup failure

Lc

DC bus under-voltage protection

PL

High discharge temperature protection

E4

DC bus over-voltage protection

PH

Overload protection

E8

Compressor phase current sensing 

citcuit error

U1

Whole unit over-current protection

E5

Compressor demagnetization protection

HE

Over phase current protection

P5

PFC protection

Hc

Compressor desynchronizing

H7

IPM Temperature Protection

P8

IPM Current protection

H5

Over-power protection

L9

Compressor phase loss/reversal 

protection

Ld

System charge shortage or blockage 

protection

F0

Frequency restricted/reduced with 

whole unit current protection

F8

Capacitor charging error

PU

Frequency restricted/reduced with IPM 

current protection

En

High pressure protection

E1

Frequency restricted/reduced with high 

discharge temperature

F9

Low pressure protection

E3

Frequency restricted/reduced with 

anti-freezing protection

FH

Compressor stalling

LE

Frequency restricted/reduced with over

-

load protection

F6

Over-speeding

LF

Frequency restricted/reduced with IPM 

temperature protection

EU

Drive board temperature sensor error

PF

Indoor unit full water error

E9

AC contactor protection

P9

Anti-freezing protection

E2

Temperature drift protection

PE

AC input voltage abnormal

PP

Sensor connection protection

Pd

Whole unit current sensing circuit error

U5

DC bus voltage drop error

U3

4-way valve reversing error

U7

Outdoor fan 1 error protection

L3

Motor stalling

H6

Outdoor fan 2 error protection

LA

PG motor zero-crossing protection

U8

Содержание IAPH301A

Страница 1: ...choosing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please visit www mirageappliances us IAPH301A OAPH301A IAPH361A OAPH361A CONFOR...

Страница 2: ...t if not avoided could result in death or serious injury Indicates a hazardous situation that if not avoided may result in minor or moderate injury Indicates important but not hazard related informati...

Страница 3: ...acuum pumping Leakage detection Check after installation Test and operation Test operation Attachment Configuration of connection pipe Pipe expanding method 1 6 7 7 8 12 14 14 15 15 18 22 23 24 24 25...

Страница 4: ...e electric shock If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Do not wash the air conditioner with...

Страница 5: ...r cord is overheating or damaged There s abnormal sound during operation Circuit break trips off frequently Air conditioner gives off burning smell Indoor unit is leaking If the air conditioner operat...

Страница 6: ...rcuit break with suitable capacity please note the following table Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner...

Страница 7: ...d personnel only The air conditioner is a first class electric appliance It must be properly grounding with specialized grounding device by a professional Please make sure it is always grounded effect...

Страница 8: ...ause personal injury or damage Select a location which is out of reach for children and far away from animals or plants If it is unavoidable please add the fence for safety purpose The indoor unit sho...

Страница 9: ...r Unit Outdoor Unit Actual product may be different from above graphics please refer to actual products air inlet Connection wire air outlet air inlet panel aux button horizontal louver air outlet NOT...

Страница 10: ...tton TEMP button I FEEL button LIGHT button CLOCK button TIMER ON TIMER OFF button SLEEP button Send signal Turbo mode 46 F heating function Set temperature Set time TIMER ON TIMER OFF Child lock Up d...

Страница 11: ...corresponding set function icons Press this button can turn on or turn off the air conditioner After turning on the air conditioner operation indicator on indoor unit s display is ON green indicator T...

Страница 12: ...r conditioner will select proper fan speed automatically according to ex factory setting Fan speed under dry mode is low speed Press this button can select up down swing angle Fan blow angle can be se...

Страница 13: ...o CLOCK TIMER ON TIMER OFF buttons Under COOL HEAT or DRY mode press this button to start up sleep function icon is displayed on remote controller Press this button again to cancel sleep function and...

Страница 14: ...indoor unit can receive the signal sent by the remote controller Press this button to turn off display light on indoor unit icon on remote controller disappears Press this button again to turn on dis...

Страница 15: ...ff according to setting time ON OFF button has no effect on setting If you don t need this function please use remote controller to cancel it Function introduction for combination buttons Energy savin...

Страница 16: ...TURBO button and the remote controller won t send signal Sleep function and 46 F heating function can t operate at the same time If 46 F heating function has been set under cooling mode press sleep b...

Страница 17: ...e two 7 AAA 1 5V dry batteries and make sure the position of polar and polar are correct 3 Reinstall the cover of battery box During operation point the remote control signal sender at the receiving w...

Страница 18: ...mode Use insulated object to press the auto button Clean and Maintenance Turn off the air conditioner and disconnect the power before cleaning the air conditioner to avoid electric shock Do not wash...

Страница 19: ...ry dirty use the water below 110 F to clean it and then put it in a shady and cool place to dry Install filter Install the filter and then close the panel cover tightly The filter should be cleaned ev...

Страница 20: ...and Maintenance Checking before use season 1 Disconnect power supply 2 Clean filter and indoor unit s panel 3 Check whether mounting bracket for outdoor unit is damaged or corroded If yes please conta...

Страница 21: ...n troller low fuzzy display and no display Check the batteries If the power of batteries is too low please replace them No display when operating remote controller Check whether remote control ler app...

Страница 22: ...indoor unit s air outlet Indoor temperature and humidity is high Because indoor air is cooled rapidly After a while indoor temperature and humidity will be decrease and mist will disappear Set tempera...

Страница 23: ...t again Outdoor unit has vapor Heating mode is turned on During defrosting under heating mode it may generate vapor which is a normal phe nomenon Water flowing noise Air conditioner is turned on or tu...

Страница 24: ...sionals for service E6 It can be eliminated after restarting the unit If not please contact qualified professionals for service F0 Please contact qualified professionals for service Note If there re o...

Страница 25: ...At least 20 At least 12 At least 118 At least 80 Space to the obstruction Space to the obstruction Space to the obstruction Space to the ceiling Space to the obstruction Space to the obstruction At le...

Страница 26: ...ure resulting in injury During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connec tion pipe If compressor starts runn...

Страница 27: ...hould be no obstruction near air inlet and air outlet 2 Select a location where the condensation water can be dispersed easily and won t affect other people 3 Select a location which is convenient to...

Страница 28: ...y the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8 The temperature of refrigerant circuit will be high please keep the interconnection cable away from the...

Страница 29: ...mounting frame on the wall with tapping screws ST4 2X25TA and then check if the frame is firmly installed by pulling the frame If the plastic expansion particle is loose please drill another fixing ho...

Страница 30: ...ding out the pipe from left or right please cut off the corresponding hole on the bottom case Step five connect the pipe indoor unit 1 Aim the pipe joint at the corre sponding bellmouth 2 Pretightenin...

Страница 31: ...in hose 1 Connect the drain hose to the outlet pipe of indoor unit 2 Bind the joint with tape outlet pipe drain hose drain hose tape outlet pipe drain hose insulating pipe Note Add insulating pipe in...

Страница 32: ...tion For the air conditioner without plug an air switch must be installed in the line The air switch should be all pole parting and the contact parting distance should be more than 3mm Outdoor unit co...

Страница 33: ...d and control wire can t be crossed or winding The drain hose should be bound at the bottom Step nine hang the indoor unit 1 Put the bound pipes in the wall pipe and then make them pass through the wa...

Страница 34: ...stalled at least 2 above the floor in order to install drain joint For the unit with cooling capacity of 2300W 5000W 6 expansion screws are needed for the unit with cooling capacity of 6000W 8000W 8 e...

Страница 35: ...ve the handle from the outdoor unit 2 Fasten the power supply cord and the connection cord to the retaining plate using the lock nut open the knock out holes if necessary 3 Connect the power supply co...

Страница 36: ...d along the wall bent reasonably and hidden possibly Min semidiameter of bending the pipe is 10cm 2 If the outdoor unit is higher than the wall hole you must set a U shaped curve in the pipe before pi...

Страница 37: ...OFF to check if pressure keeps stable If not you must look for leakage fix and try again 5 If vacuum level is stable use an Allen wrench to open gas and liquid valves completely to let refrigerant fi...

Страница 38: ...the speci cation It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and outlet It may cause insuf cient cooling heat ing capacity The dust and sundries caused dur...

Страница 39: ...ft 65 ft 48000Btu h 14064W 98 ft 65 ft 4 The additional refrigerant oil and refrigerant charging required after prolonging connection pipe After the length of connection pipe is prolonged for 32 ft at...

Страница 40: ...7C R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe Gas pipe Cooling only oz ft Cooling and heating oz ft 1 4 3 8 or 1 2 0 161 0 215 1 4 or 3 8 5 8 or 3 4 0 161 0 537 1 2...

Страница 41: ...move the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe E Expand the port Expand the port with expander Note A is different according to the diameter pleas...

Страница 42: ...5 Compressor demagnetization protection HE Over phase current protection P5 PFC protection Hc Compressor desynchronizing H7 IPM Temperature Protection P8 IPM Current protection H5 Over power protectio...

Страница 43: ...6700 Gateway Park Dr Unit 6 San Diego CA 92154 Ph 619 426 0033 mirageappliances us...

Отзывы: