2. Electrical
WARNING: THIS APPLIANCE MUST BE EARTHED.
All electrical installations must comply with current IEE regulations and be undertaken
by a qualified person.
2.1.
The power to the pump should be through a double pole, switched, fused
connection unit or equivalent with a 5A fuse (Refer to Figure 6), the contact
separation in each pole should be at least 3mm. A cable with a minimum core
area of 0.75mm
2
should be used from the fuse to the pump.
2.2.
Remove the terminal cover (single screw) and connect the electrical supply
and, only if necessary, connect the momentary action switch to the
appropriate terminals (Refer to Section 2, Operation):
L = Brown, N = Blue, E = Yellow/Green, FS = Flow Switch and External
Switching. (Refer to Figure 6). Ensure that the cable gland nut is tightened
to provide strain relief.
Other hot water
services
DHW
Cistern
Pump
Unsuitable System Layout
Figure 5