SNMP-32 Series

 

(Web-based monitoring SNMP card)

 

 

 
 

User’s Manual 

 
 
 

 
 
 

 
 

 
 
 

 
 
 
 

 
 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

34000241 Rev1 

Содержание SNMP-32 Series

Страница 1: ...SNMP 32 Series Web based monitoring SNMP card User s Manual 34000241 Rev1 ...

Страница 2: ...tion PPP 15 4 7 Configuration Web Telnet 15 4 8 Configuration System Time 16 4 9 Log Information Event 16 4 10 Log Information Data 18 5 Firmware Upgrade Procedure 19 6 Telnet 21 6 1 Telnet Configuration 21 7 Connected Device 23 7 1 Uninterruptible Power Supply UPS 23 7 2 Remote Power Manager RPM 29 7 3 Current Probe Sensor CPS 32 7 4 Temp Hum32 Probe ENV 33 7 5 Automatic Transfer Switch ATS 34 8 ...

Страница 3: ... of Communications Trademarks MINUTEMAN is a registered trademark of Para Systems Inc All other trademarks are the property of their respective holders Conventions used in this guide This guide uses these conventions Bold italic print as shown in this example indicates field names menu items or values in the SNMP 32 Card software agent Bold print as shown in this example indicates filenames direct...

Страница 4: ...SMTP protocols The user can use a SNMP manager or a Web browser to monitor the UPS through a network Multiple OS support As long as there is Network Management software present Remote setup support Once an IP address is assigned the rest can be setup remotely through Telnet or a Browser Remote monitoring Monitors the status of one UPS from a remote workstation Web browser or NMS Remote Control Tur...

Страница 5: ...tate with UPS Yellow LED Action Correspondence state with the Network LAN Port LED Table Yellow Green Status OFF Solid ON Network Connectivity speed is 100M OFF Flashing Transmitting data Solid ON OFF Connectivity speed is 10M Flashing OFF Transmitting data Green LED Connectivity 100M Yellow LED Connectivity 10M 1 2 Package Contents Internal SNMP 32 card Package Contents The contents of the packag...

Страница 6: ...NMP 32 card and the RPM Remote Power Manager When the RPM is connected to the network with the SNMP 32L card the system manager could check each device s condition via a Web Browser The manager could monitor and control the devices by simply inputting the IP address of the SNMP 32L card When there is an abnormal power condition the SNMP 32L card will send the trap information to the system manager...

Страница 7: ...Setup Procedure Fig 4 External SNMP 32 Card SNMP 32L Only External SNMP 32 card SNMP 32L Only NOTE The SNMP 32 cards are designed to be Hot Swappable but there is a remote chance that when Hot Swapping the SNMP 32 card that the UPS will shutdown MINUTEMAN recommends following steps 1 through 11 when installing the SNMP 32 card but to hot swap skip to step number 3 and omit steps 9 10 1 Turn off al...

Страница 8: ...ty program Fig 5 Fig 5 SNMP Utility Group 4 Once the SNMP Utility is open the SNMP Utility will search for the network adapter automatically or click on Network Selection from the main page The screen will display the network adapter that was located Click on the network adapter and then press OK to return to the main page of SNMP Utility Fig 6 Fig 6 SNMP Utility Network Selection 5 The SNMP Utili...

Страница 9: ...t the correct password B Management Protocol Not required The HTTP port and the Telnet port can be changed for security purposes When the HTTP port or the Telnet port is changed then the full IP address must be entered to access the SNMP 32 card Example Change the HTTP port to 81 and then you must enter the IP address 192 168 0 5 81 to access the SNMP 32 card Change the Telnet port to 24 and then ...

Страница 10: ...ord was not entered in the Set Up Procedure then click OK Fig 10 NOTE There is no default User Name or Password Fig 10 SNMP 32 card Login Screen 4 1 Main Menu On the left hand side of the Main Menu there are four categories Fig 11 1 Information Provides the information about the connected Device 2 Configuration Configure the network and devices setting 3 Log Information Record the events and data ...

Страница 11: ...MAC address is provided by SNMP 32 card The other information is the user settings from the SNMP Utility Configuration pages Fig 12 System Status Screen 4 3 Configuration Network This screen is to set the Network settings Fig 13 NOTE SNMP 32 card will reboot after making changes to any of the following sections 1 IP Address This section is to set the IP address 2 Subnet Mask This section is to set...

Страница 12: ... name for the SNMP 32 card B System Contact This section is to input the name of the administrator C System Location This section is to input the name of the location of the SNMP 32 card 2 Access Control A Manager IP Address This section is to set the IP address that the administrator can manage SNMP 32 card from the specific IP address It is valid for up to eight IP addresses is the default setti...

Страница 13: ...hree levels for the Trap receiver z Information To receive all traps z Warning To receive only warning and severe traps z Severe To receive only severe traps Please refer to NMS User s Manual for Trap levels D Acceptance This section is for authorizing the receiver to receive a trap or not E Description This section is for an administrator to make notes F Events Fig 15 This section is to select ev...

Страница 14: ...erver requires authentication E Send Email When an Event Occurs This section is to set the SNMP 32 card to send an email when an event occurs 2 Recipient s Email Address for Event Log This section is to set the email addresses for the recipients to receive an email when an event occurs There can be up to eight recipients A Event This section is to select which events for the recipients to receive ...

Страница 15: ...to input the user name and password to view the Web pages B Password This section is to set a password for the SNMP 32 card s Web pages The users have to input the password and the user name to view the Web pages C Permission This section is to set the specified user s authorizations of Read or Read Write D IP Filter This section is to set a specific IP address for a certain user This user can onl...

Страница 16: ...m ss This section is to set the system time manually for the SNMP 32 card Fig 19 System Time Screen 4 9 Log Information Event 1 Event Log This screen shows a log of events for the connected device Fig 20 The log displays the Date Time of the event the connected device and a description of the event The SNMP 32 card can log up to 500 events When the 500 event limit is reached SNMP 32 card will dele...

Страница 17: ...mental Humidity Underrun CPS Event List CPS Communication Lost Current Out of Threshold 1 Current Out of Threshold 2 ATS Event List Switch Input Power Fig 20 Event Log Screen 2 Save Event Log This function is to save the current event log to another file for maintaining an Event Log History Fig 21 Fig 21 Save Event Log Screen ...

Страница 18: ...ut Loading Battery Capacity and the Battery Temperature The SNMP 32 card can log up to 500 events When the 500 event limit is reached SNMP 32 card will delete the earliest log record and continue logging new Data Fig 22 Data Log Screen 2 Save Data Log This function is to save the current event log to another file for maintaining a Data Log History Fig 23 Fig 23 Save Event Log Screen ...

Страница 19: ...ll search for the network adapter automatically or click on Network Selection from the main page The screen will display the network adapter that was located Click on the network adapter and then press OK to return to the main page of SNMP Utility Fig 25 Fig 25 SNMP Utility Network Selection 4 The SNMP Utility will then search for and display all of the SNMP 32 cards that are on your LAN Select th...

Страница 20: ...llow LEDs will flash alternately meaning the firmware upgrade is in process Fig 27 Fig 27 SNMP Utility Download Firmware 6 Once the Firmware Upgrade is complete the SNMP 32 card will auto reboot Fig 28 Click Cancel and then close the SNMP Utility program The SNMP 32 card is ready for normal operation Fig 28 SNMP Utility Download Firmware Complete ...

Страница 21: ...dows click Run then input Telnet and the SNMP 32 card s IP Address Then click OK Fig 29 Fig 29 Telnet Startup 2 Telnet connection successful Fig 30 Press any key to continue Fig 30 Telnet Connection 3 If you entered a User Name and a Password enter them now If you did not enter a User Name and a Password hit enter Fig 31 Fig 31 Telnet Login ...

Страница 22: ...P address of the PC must be added in this list of SNMP 32 card Note The configuration of Set SNMP Trap Receiver is only used for SNMP Network Manager Set System Time Time Server This function is for setting the System Date and the System Time Set Web and Telnet User Account This function is for setting the user s account authorization Set Email This function is for setting the email accounts to re...

Страница 23: ...ormation Fig 33 The UPS provides the values shown or they are user settings from the Configuration pages UPS Information The UPS provides the following information the Manufacturer the Firmware Version and the Model Battery Information The UPS provides the values shown or they are user settings from the Configuration pages Rating Information The UPS provides the values shown or they are user setti...

Страница 24: ...to show the UPS input status AC Status Input Voltage Input Frequency The values will be shown in red when an abnormal condition occurs Output Status This section is to show the UPS output status Output Voltage Output Status UPS Loading The values will be shown in red when an abnormal condition occurs Battery Status This section is to show the UPS Battery Status Temperature Battery Status Battery C...

Страница 25: ...e UPS will switch back to the normal AC mode Cancel Test The Cancel Test function is to abort a test while the test is in progress Shutdown UPS Battery mode only Selecting Shutdown UPS will turn off the UPS This function can only be performed in the battery mode The UPS will automatically restart when AC returns Put UPS in Sleep mode for XX minutes When the UPS is in the Sleep mode it will not pro...

Страница 26: ...w Screen Clicking on the Setting button the user can set the Upper Threshold and the Lower Threshold for the Output Voltage the Output Load and the Input Voltage Fig 37 Fig 37 Set Thresholds Screen Clicking on the Log Graphics button the user can observe the Input Voltage Output Voltage Frequency Loading Capacity and Temperature appearing within the X Y coordinates Fig 38 Fig 38 Log Graphics Scree...

Страница 27: ...erform a test Warning Threshold Value Time Out of Connection Lost The user can set the time interval for a warning of a lost connection Critical Loading The user can set the warning threshold for an Overload condition Fig 39 UPS Settings Screen 6 UPS Schedule This screen allows the user to schedule a shutdown and a restart of the UPS Fig 40 To add a new schedule select the New button To make chang...

Страница 28: ...s only supported when the UPS or ENV is connected to the RPM Fig 42 RPM Action Screen 1 After selecting the New button the following page will appear Fig 43 Events Select The user can select which event to start the Action Events Action The user can select to perform the Action when the event occurs or when the event is removed RPM The user can select which RPM to perform the Action Outlet The use...

Страница 29: ...Safe Shutdown The outlet can only be controlled via the Web page The outlet will be turned off after XX number of seconds by clicking on the outlet icon see RPM Setting screen Safe Reboot The outlet can only be controlled via the Web page The outlet will turned on reboot after XX number of seconds see RPM Setting screen On Off This is the current state of the outlet on off Outlet Icon Clicking on ...

Страница 30: ...ontrol Type Instant Shutdown When the outlet is turned off the outlet will shutdown immediately Safe Shutdown When the outlet is turned off there will be a time delay before the outlet turns off according to the value in the Power Off Delay field Safe Reboot When the outlet is turned off there will be a time delay before the outlet turns on again according to the value in the Power Resume Delay fi...

Страница 31: ... restart configuration and then click the Save button RPM The user can select which RPM to perform the Action RPM01 RPM16 Outlet The user can select which outlet to perform the Action Outlet Action The user can select to turn on the RPM s outlet or turn off the RPM s outlet Date The user can configure the RPM to perform the Action Once on the specified date format mm dd yyyy or the RPM can be conf...

Страница 32: ...is screen shows the electrical current detected by CPS and indicates if the current is out of the preset range Fig 48 CPS Status Screen 2 CPS Configuration Fig 49 Name The user can rename the CPS Threshold 1 The user can set the out of tolerance value for the first phase Threshold 2 The user can set the out of tolerance value for the second phase Fig 49 CPS Configuration Screen ...

Страница 33: ...rval for refreshing the ENV Status screen When there is an environmental condition that is out of tolerance it will appear in red Fig 50 ENV Status Screen 2 ENV Configuration Fig 51 The user can define the out of tolerance range for the temperature and the humidity If the temperature or humidity exceeds the out of tolerance range the SNMP 32 card can be configured to perform an action such as emai...

Страница 34: ... is being used Clicking on the ICON can switch the input power source from Input Power Source A to Input Power Source B Fig 52 Automatic Transfer Switch Screen 2 ATS Configuration Fig 53 Identification The user can define the name of the ATS Input Power Source A The user can define the name of the Input Power Source A Input Power Source B The user can define the name of the Input Power Source B Fi...

Страница 35: ... copied earlier 6 Select OK Add the SNMP 32 card Object to the Management Map 1 Select the submap then Edit Add Object 2 Select the group computer 3 With the middle or opposite mouse button drag the generic symbol subclass device to the submap 4 Enter a name for the object in the Selection and Label fields of the Add Object box 5 Highlight IP Map from Object Attributes group 6 Select Set Object At...

Страница 36: ...ather than in binary notation Dotted decimal notation divides the 32 bit value into four 8 bit groups or octets and separates each octet with a period For example 199 217 132 1 is an IP address in dotted decimal notation To accommodate networks of different sizes the IP address has three divisions Classes A for large B for medium and C for small The difference among the network classes is the numb...

Страница 37: ...ther s IP packets set the subnet mask to 255 255 0 0 If you want the devices on a single sub network only to receive IP packets from other devices on its own sub network set the subnet mask to 255 255 255 0 for the devices on that sub network Subnet Mask Routing and Filtering 0 0 0 0 IP packets are transmitted to all devices 255 0 0 0 IP packets are only transmitted to devices that are IP that s f...

Страница 38: ...ate and the LEDs are not illuminated Solution Make sure the UPS is turned ON Solution Make sure that the external power adaptor is plugged into the UPS Solution The power adaptor could be bad Contact Tech Support Solution Make sure this is not a scheduled shutdown Problem The SNMP 32 card will not communicate and all of the LEDs are ON Solution There has been a collision of the packets The SNMP 32...

Страница 39: ...Company Name Address City State ZIP code Contact Person s Name Phone Number If you are a consultant Consultant Name Phone Number Fax Number Computer System Operating System and version System Manufacturer System Model Number NMS name and revision number UPS Model Name Number Serial Number Type of SNMP Card internal or external What are the symptoms Technical Support Please have the information lis...

Страница 40: ... to the product s operating manual or other written instructions Any technical advice furnished before or after delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but it is used at the recipient s sole risk EXCEPT AS PROVIDED HEREIN PARA SYSTEMS MAKES NO WARRANTIES...