CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source 

a

nd there is an acceptable AC voltage present.  NOTE:  The input

circuit breaker MUST be in the on position for the 208V models.  It is recom-
mended that the UPS's batteries be charged for a minimum of 4 hours before
use.  The UPS may be used immediately, however, the “On-Battery” runtime
may be less than normally expected.  NOTE:  If the UPS is going to be out of
service or stored for a prolonged period of time, the batteries must be recharged
for at least twenty-four hours every ninety days.

CHECKING THE SITE WIRING FAULT (120V Models)
After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the front
panel of the UPS.  If the SWF LED is illuminated, the UPS is plugged into an
improperly wired AC outlet.  If the UPS indicates a Site Wiring Fault (SWF),
have a Qualified Electrician correct the problem.

COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The Power Monitoring Software and interface cables can be used with the UPS.
Use only the interface cables that come with these UPSs.  Connect the inter-
face cable (Serial or USB) to the appropriate communications port on the rear
panel of the UPS.  Connect the other end of the cable to the device that will be
monitoring/controlling the UPS.  NOTE:  Connecting to the Communications
Port is optional.  The UPS works properly without this connection.

CONNECTING THE UPS TO AN AC SOURCE
Plug the UPS into a two pole, three wire, grounded receptacle only.  Do not use
extension cords, adapter plugs, or surge strips.

NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)
Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the
RJ11/45 modular connectors on the rear panel of the UPS.  This connection will
require another length of telephone or network cable.  The cable coming from
the telephone service or networked system is connected to the port marked
“IN”.  The equipment to be protected is connected to the port marked "OUT".
NOTE:  Connecting to the Network/Phone/Fax/Modem modular connectors is
optional.  The UPS works properly without this connection.

CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS.
Do not use extension cords, adapter plugs or surge strips on the output of the
UPS.  Ensure that you do not exceed the maximum output rating of the UPS
(refer to the information label or the Electrical Specifications in this manual).

CAUTION!

DO NOT connect a laser printer to the output receptacles on the
UPS, unless the UPS is rated 2000VA or greater.  A laser printer
draws significantly more power when printing than at idle and
may overload the UPS.

RJ11 REPO (Remote Emergency Power Off) PORT (OPTIONAL)
Connect one end of the RJ11 cable to the REPO port and the other end of the
RJ11 cable to the EPO switch.  In the AC or the Battery mode short pin4 to pin5
for approximately 0.5-seconds to shutdown the UPS.  The UPS must be turned
off and then back on again to restart the UPS.  NOTE:  Connecting to the
REPO port is optional.  The UPS works properly without this connection.

Содержание Enterprise Plus E1000RM2U

Страница 1: ...User s Manual Enterprise Plus Series UPS...

Страница 2: ...d Indicators 6 3 Installation 9 4 Operation 15 5 Troubleshooting 18 6 Replacing the Battery 19 7 Obtaining Service 22 8 Specifications 23 9 Configurable Parameters Settings 25 10 Limited Product Warra...

Страница 3: ...ng installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance Included is information on customer support and factory ser...

Страница 4: ...ect the UPS to a two pole three wire grounding AC wall outlet The receptacle must be connected to the appropriate branch protection circuit breaker or fuse Connection to any other type of receptacle m...

Страница 5: ...imits are designed to provide reasonable protection against such interference in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly th...

Страница 6: ...ected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes auto t...

Страница 7: ...s The Buck yellow LED illuminates in a blinking state when the UPS is operating in the Buck mode The Buck LED will extinguish when operating in the AC normal Boost and Battery modes The Fault red LED...

Страница 8: ...D 70 70 battery capacity green yellow LED will be yellow and illuminated until the battery s capacity drops below 60 ca pacity and then it will extinguish LED 50 50 battery capacity green yellow LED w...

Страница 9: ...ding Function NOTE The locking recptacle is not on all models 8 The input circuit breaker will trip in the event the load exceeds the UPS s power rating 9 The input power cord 120V models TheAC Power...

Страница 10: ...perating and Storage Relative Humidity 95 non condensing Storage Temperature 15 to 45 degrees C 5 to 113 degrees F Storage Elevation 0 to 15 000m 0 to 50 000 ft INSTALLATION Be sure to read the instal...

Страница 11: ...pping box and set on the floor or a bench top 2 Remove the front panel retaining screws 3 Lay the front panel on top of the UPS 4 Verify proper polarity Connect the battery connectors red and black to...

Страница 12: ...t of the UPS NOTE The mounting brackets can also be mounted in the middle of the UPS 2 Align the mounting bracket with the mounting bracket screw holes 3 Attach the mounting bracket with the retaining...

Страница 13: ...ke sure that the UPS is stable 3 The LED face plate can be rotated to read in the up right position Remove the front panel from the UPS On the backside of the front panel push the LED face plate outwa...

Страница 14: ...les and attach w ith the six retaining screws 3 Use the template to mark the screw hole position on the wall CAUTION you sh ould always were protective gear for your hands and eyes when operating powe...

Страница 15: ...g the UPS into a two pole three wire grounded receptacle only Do not use extension cords adapter plugs or surge strips NETWORK PHONE FAX MODEM PROTECTION CONNECTION OPTIONAL Connect a 10 100 Base T ne...

Страница 16: ...power returns or is at an acceptable level the UPS will auto matically transfer back to the AC normal mode and start recharging the batter ies During an extended outage when there is approximately tw...

Страница 17: ...208VAC default or 127VAC 240VAC Changing the Inverter On Battery output voltage to 127VAC will also change the Buck setpoint Changing the Inverter On Battery output volt age to 240VAC will also change...

Страница 18: ...Alarm POWER MONITORING SOFTWARE The UPS comes with a Power Monitoring Software CD See the software CD for the installation of the Power Monitoring Software USB PORT The USB protocol is HID The HID US...

Страница 19: ...Site Wiring Fault LED is illuminated Have a Qualified Electrician correct the service wiring The batteries may be weak or at the end of useful service life Charge the batteries for 8 hours and retest...

Страница 20: ...ry system can still present a risk of electrical shock These batteries produce sufficient current to burn wire or tools very rapidly producing molten metal Observe these precautions when replacing the...

Страница 21: ...ition for the 208V models 3 Unplug the UPS s AC power cord from the AC wall outlet 4 Unplug the equipment from the output receptacles of the UPS 5 Unplug the computer interface cable from the rear pan...

Страница 22: ...erify proper polarity Reconnect the battery negative black wire 19 Verify proper polarity Reconnect the battery positive red wire 20 Slide the battery module into the UPS 21 Verify proper polarity Rec...

Страница 23: ...os sible F A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you...

Страница 24: ...E1000RM2U E750RM2U Model Number SYSTEM SPECIFICATIONS Voltage Range Topology Line Interactive Sine Wave OUTPUT NON BATTERYOPERATION INPUT Number of Phase Single 1 2W G Nominal Voltage 120VAC 208VAC L...

Страница 25: ...ed ANSI C62 41 Cat A 6 kV Surge Response Time Surge Current Capability Surge Energy Rating 800 J 600 J 0 ns instantaneous normal mode 5 ns common mode 5 normal and common mode EMI RFI suppression 45 d...

Страница 26: ...reflect actual number of days experience in your environment or leave factory default Enter the current date when replacing batteries Use this function to uniquely identify the UPS in your network con...

Страница 27: ...properly registered the product within 10 days of purchase The warranty shall be void if a the equipment is damaged by the customer is improperly used is subjected to an adverse operating environment...

Страница 28: ...arties or otherwise The sole and exclusive remedy for breach of any warranty expressed or implied concerning Para Systems s prod ucts and the only obligation of Para Systems hereunder shall be the rep...

Страница 29: ...ve Carrollton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No E750RM2U Y E1000RM2U Y E1500RM2U Y E2000RM2U Y E3000RM2U Y I hereby declare that the equipment specified abo...

Страница 30: ...29 Notes English...

Страница 31: ...30 English Notes...

Страница 32: ...Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000271...

Отзывы: