BUS Over Voltage
Alarm Code:21
Indicates that the UPS
get BUS over voltage
fault because of BUS.
The UPS transfers to Bypass
mode if supporting the load
BUS Under Voltage
Alarm Code:22
Indicates that the UPS
get BUS under voltage
fault
The UPS transfers to Bypass
mode if supporting the load
BUS Unbalance
Alarm Code:23
Indicates that the
positive BUS voltage and
negative BUS voltage
are too lopsided to fault
The UPS transfers to Bypass
mode if supporting the load
BUS Short
Alarm Code:24
Indicates that the BUS
voltage decrease very
fast
Contact your service
representative
BUS Softstart Fail
Alarm Code:25
Indicates that the BUS
could not soft start
successfully
Contact your service
representative
Inv Over Voltage
Alarm Code:32
Indicates that the UPS
get invert over voltage
fault
The UPS transfers to Bypass
mode if supporting the load
Inv Under Volatge
Alarm Code:33
Indicates that the UPS
get inverter under
voltage fault
The UPS transfers to Bypass
mode if supporting the load
Inv Softstart Fail
Alarm Code:34
Indicates that the inverter
could not soft start
successfully
Contact your service
representative
Charger Fail
Alarm Code:15
Indicates that the UPS
has confirmed the
charger has failed
The UPS turns off the
charger until the next power
recycle. Contact your service
representative
Battery Over Voltage
Alarm Code:16
Indicates that the battery
voltage is too high
The UPS will turn off the
charger until the battery
voltage is normal
Fatal eeprom Fault
Alarm Code:A3
Indicates that the UPS
could not read eeprom
successfully
Contact your service
representative
Содержание 6-10KVA Tower
Страница 1: ...USER MANUAL ONLINE UPS 6 10KVA Rack Tower ...
Страница 24: ...21 Frequency converter without Bypass AC input ...
Страница 31: ...28 Figure 26 Parallel systerm wiring diagram of 6K 10K ...
Страница 40: ...37 Fig 5 14 Main menu tree ...
Страница 47: ...44 Example set rated output voltage value Fig 5 22 Set rated output voltage value ...
Страница 61: ...58 614 08090 00 ...