22
Function No.
Item
Setting
value
Details
F-15
Rotation speed stabilization
filter
No. of averaging
0
No. of moving-average samples: 1
1
No. of moving-average samples: 2
2
No. of moving-average samples: 4
3
No. of moving-average samples: 8
4
No. of moving-average samples: 10
5
No. of moving-average samples: 12
●
6
No. of moving-average samples: 14
7
No. of moving-average samples: 16
8
No. of moving-average samples: 32
F-16
Rotation speed stabilization
filter
Time width setting
000~999
Unit: 10 ms
000: Rotation speed stabilization filter off
●
000
F-17
Rotation speed stabilization
filter
Data width setting
00~99
Unit: DIGIT
00: Rotation speed stabilization filter off
●
20
F-18 Key
lock
0000
~1111
●
0000
0: Off
1: On
10
0
digit:
10
1
digit:
10
2
digit:
10
3
digit:
F-19 Polarity
change
●
0
Torque in counter-clockwise direction is
positive.
1
Torque in clockwise direction is positive.
F-20 CHECK
value
0~20
Refer to Section 9-2-3.
●
16
F-21
Torque analog output
Max. display value
1~99 999
Unit: DIGIT
●
10 000
F-22
Rotation speed analog output
Max. display value
1~27 500
Unit: DIGIT
●
25 000
F-23
Rotation direction polarity
●
0
+
1 -
F-24
Rotation detection input signal
format
●
0
Off
1
Measured using 2 rotation detectors
2
Measured using 1 rotation detector.
Rotation direction detected using external
input signal
3
Measured using 1 rotation detector.
Rotation direction cannot be detected.