Parameter table (continued)
Parameter
Selection
Description
[linear]
In the event of a negative weight, the analog
output is retained. This is only possible if the
output value for the zero weight is >0 mA.
[0 mA]
In the event of a negative weight, the analog
output is set to 0 mA.
[4 mA]
In the event of a negative weight, the analog
output is set to 4 mA.
[On <0]
[20 mA]
In the event of a negative weight, the analog
output is set to 20 mA.
[linear]
In the event of a weight >Max, the analog out
put is retained. This is only possible if the out
put value for Max is <20 mA.
[0 mA]
In the event of a weight >Max, the output is set
to 0 mA.
[4 mA]
In the event of a weight >Max, the output is set
to 4 mA.
[On > Max]
[20 mA]
In the event of a weight >Max, the output is set
to 20 mA.
[Analog value]
Input: fixed analog val
ue
Only possible if [Transparent] mode is selected.
[Weight value at
0/4 mA]
Input: Weight value
Weight value at which the analog output
should display 0 mA.
or
Weight value at which the analog output
should display 4 mA (for the analog range 4…
20 mA).
[Weight value at
20 mA]
Input: Weight value
Weight value at which the analog output
should display 20 mA.
[Adjust for 4 mA]
Input: Weight value
Value at 4 mA.
[Adjust for 20 mA]
Input: Weight value
Value at 20 mA.