Specifications
1-Phase
1 or 3-Phase
Max Continuous
AC
Input
Output
Max
Output
Amps
Drive
(VAC)
(VAC)
HP
Current (AC)
In
VFD01-230AC
230
230
¼
1.2
3
VFD01-D230AC
*
115 / 230
230
¼
1.2
7 / 3
VFD02-115AC
115
115
¼
2.4
7
VFD02-230AC
230
230
½
2.4
7
VFD02-D230AC
*
115 / 230
230
½
2.4
10 / 7
VFD04-115AC
115
115
½
4.0
†
10
VFD04-230AC
230
230
1
4.0
†
10
VFD04-D230AC
*
115 / 230
230
1
4.0
†
15 / 10
*
Connect only 115 VAC line input to the 115 VAC terminals. Application of 230 VAC line input when set for 115
VAC will result in severe damage to the motor and drive, and possible explosion and injury.
† Derate current by 2% per degree if the operating temperature is above 40°C. Under no circumstances may the
ambient temperature exceed 55° C.
AC Voltage Input Range
VFDxx-115AC drives
115 VAC ± 10%, 50/60 Hz single phase
VFDxx-230AC drives
230 VAC ± 10%, 50/60 Hz single phase
VFDxx-D230AC drives
115/230 VAC ± 10%, 50/60 Hz single phase
Standard Carrier Frequency
16 KHz
Output Frequency Range
0 – 120 Hz
Adjustable Maximum Output Frequency Range
30 – 120 Hz
Acceleration Time Range
1 – 12 seconds
Deceleration Time Range
1 – 12 seconds
Analog Input Voltage Range (signal must be isolated; S1 [-] to S2 [+])
0 – 5VDC**
Input Impedance, S1 to S2
~ 100K ohms
Vibration
0.5G max (20 – 50 Hz)
0.1G max (> 50 Hz)
Weight
1.2 lb
Ambient Operating Temperature Range
10° – 40° C
** An isolation board option that allows for a non-isolated 0 - 5 VDC, 0 - 10 VDC, or 4 - 20 mA input signal is
available (-PCM option). The option board is installed directly above the main board, maintaining the same
footprint and dimensions. Call the factory for more information regarding the -PCM option.