7
6
NOTE: To prevent damage to the cable, do not exceed the recommended pipe diameters.
Cable installation
Inserting cable into drum (Fig. 1 & 2)
1.
Make a 15° to 30° bend approximately
1 inch from the tail end of the cable
(See Fig. 1). This will aid in seating
the cable into the drum.
Fig. 2
Cable
Size
1/4"
5/16"
5/16"
3/8"
Pipe
Dia.
1 1/4"-1 1/2"
1 1/4"-1 1/2"
1 1/4"-1 1/2"
1 1/2" -2"
Selecting the proper cable
Cable
Style
Steel Coreless
Steel Coreless
Steel Inner-core
Steel Inner Core
Additional Applications
Trap & Drain Lines
Trap & Drain Lines
Trap & Drain Lines"
Drain lines & Boiler Tube Cleaning
TOOL ASSEMBLY
2.
Hold the drain cleaner firmly. Loosen
the chuck and insert the cable approxi-
mately 10 to 12 inches into the drum
(See Fig. 2). To prevent kinking, insert
the complete cable into the drum, 10 to
12 inches at a time, leaving only the
bulb or the enlarge head exposed.
Fig. 1
1"
15° to 30°
To reduce the risk of injury, al-
ways unplug the tool before at-
taching or removing accessories.
Use only specifically recom-
mended accessories. Others may
be hazardous.
WARNING!
Grounded tools require a three wire ex-
tension cord. Double insulated tools can
use either a two or three wire extension
cord. As the distance from the supply out-
let increases, you must use a heavier
gauge extension cord. Using extension
cords with inadequately sized wire causes
a serious drop in voltage, resulting in loss
of power and possible tool damage. Refer
to the table shown to determine the re-
quired minimum wire size.
The smaller the gauge number of the wire,
the greater the capacity of the cord. For
example, a 14 gauge cord can carry a
higher current than a 16 gauge cord. When
using more than one extension cord to make
up the total length, be sure each cord con-
tains at least the minimum wire size re-
quired. If you are using one extension cord
for more than one tool, add the nameplate
amperes and use the sum to determine the
required minimum wire size.
Guidelines for Using Extension Cords
•
If you are using an extension cord out-
doors, be sure it is marked with the
suffix “W-A” (“W” in Canada) to indi-
cate that it is acceptable for outdoor
use.
•
Be sure your extension cord is prop-
erly wired and in good electrical
condition. Always replace a damaged
extension cord or have it repaired by
a qualified person before using it.
•
Protect your extension cords from
sharp objects, excessive heat and
damp or wet areas.
READ AND SAVE ALL INSTRUCTIONS FOR FUTURE USE.
Recommended Minimum Wire
Gauge for Extension Cords*
Extension Cord Length
* Based on limiting the line voltage drop to
five volts at 150% of the rated amperes.
Nameplate
A m p e r e s
0 - 2.0
2.1 - 3.4
3.5 - 5.0
5.1 - 7.0
7.1 - 12.0
12.1 - 16.0
16.1 - 20.0
25'
18
18
18
18
16
14
12
75'
18
18
16
14
12
10
100'
18
16
14
12
10
150'
16
14
12
12
50'
18
18
18
16
14
12
10
EXTENSION CORDS