background image

INSTALLATION 
1. Place pump in a location 

convenient to the appliance drain 
line. 

2. Pump may be mounted level to 

ensure proper operation. Attach 
directly to air conditioning unit, 
furnace,  wall, or placed on the 
floor. Use the provided template 
for locating screw . 

3. For ease of installation, the pump 

reservoir can be easily removed 
from the pump. The pump lid can 
then be rotated 180 degrees to 
orient the location of the cord and 
discharge line to opposite ends. 

4. Connect the condensate drain into 

one of the four top inlets, using 
flexible tubing or PVC pipe; OR 
hard plumb directly into the 
bottom of the pump using the 
optional bottom inlet. 

5. Make sure that the inlet tubing is 

fastened securely so that it cannot 
come out of the pump intake port.  

6. Connect discharge tubing to the pump, run tubing from pump to desired 

drain location. Pump discharge check valve is made for use with 3/8” ID 
plastic tubing.  

7. Press tubing on discharge check valve and clamp tight with a ½” hose clamp. 
8. Run tubing to necessary height, making sure that the height does not 

exceed the pumps maximum lift (15’KTP-15, 19’ KTP-20). 

9. From maximum height slope tubing slightly downwards and/or make an 

inverted “U” trap at the highest point, creating a siphon to maximize pump 
performance. (Figure 1) 

10. Condensate can be drained out a window, along the air conditioner freon 

line to outdoors, to a french drain or floor drain, sump pit, or to a laundry tub 
or sink. (Leave an air gap between the end of the discharge tube and drain).  

11. Comply with all local codes for discharge water requirements. 

Optional Bottom Inlet Instructions: 

(This step is for convenience only) (Figure 3) 

Place the pump on a flat surface.  Use a flat screw driver to knock out additional ports as 
needed.  There are three other inlet ports on the lid and one on the lower side.  The bottom 
inlet needs to be hard plumbed.  This is done by applying PVC cement to the bottom inlet an 
inserting ¾” PVC piping. 

CONNECTION OF AUXILIARY SAFETY SWITCH

—MODELS 

KTP-15X, KTP-20X are equipped with an auxiliary safety 
switch which can be wired to shut down the AC/furnace 
and prevent pump overflow if the drain line becomes 
blocked, or the pump fail. The switch can also be wired as 
an alarm switch for installations that do not allow 
interruption of heating or cooling. 

To Wire as a Shut-off switch: 

(Figure 4) 

1.    Disconnect power to the AC/furnace and unplug condensate pump before connecting the safety switch. 
2.    Disconnect the “Red” wire from the AC/furnace bundle coming from the thermostat. 
3.    Connect the red wire to one of the two yellow wire leads coming off the condensate pump, using a wire nut. 
4.    Connect the other yellow wire lead from the condensate pump to the red terminal on the AC/Furnace block. 
5.    If additional wire is needed to connect the pump to the thermostat line, use minimum 18AWG copper wire, rated at 

105 degrees C. Comply with all local wiring codes.  

Hose Clamp

3/8" ID Tubing
To Floor Drain

or Laundry Tub.

Ceiling and Joists

Grounded

Outlet

Discharge tube should

slope down toward

outlet if possible

Do not kink tube !

Cut tubing at an angle
so that bottom of 
reservoir doesn't close it.
Be sure tubing does not
interfere with float.

Figure 1 

Condensate

Pump

Yellow

Yellow

R

ed

W

hi

te

G

re

e

n

Y

el

lo

w

Wire Nut

From Thermostat

Furnace / A.C.

Figure 4 

Figure 2 

Figure 3 

Отзывы: