Pellerin Milnor Corporation
4. Return to minimum fire (MVP = 001) and main air damper position 2 (D = 2).
5. Confirm that the pressure is within the range specified in
. If not, see below
notice.
NOTICE:
Insufficient combustion air—If you measured insufficient differential pres-
sure, go no further. There is a problem with the combustion air supply, perhaps with the
combustion air motor or the ratio air actuator. You will not be able to complete the adjust-
ment steps.
• Troubleshoot then restart the adjustment steps.
7.7.
Step 7: Set the maximum fire differential gas pressure
BNDGUM02.T07 0000342546 B.2 A.4 5/13/21 8:47 AM Released
1. See
. Connect the manometer across
GFH
and
GFL
.
2. Loosen the locking screw (item 4) on
VB
.
3. See caution statement above and
. Command maximum fire (MVP = 255)
and main air damper fully open (D = 0).
4. Take note of the manometer pressure reading.
5. Command minimum fire (MVP = 001) and main air damper position 2 (D = 2).
6. In Step 1, you set the manual butterfly valve fully open. On any 64_TG1 model, confirm that
the differential pressure is within or above the range given in
. If not, see be-
low notice. On any 76_TG1 or 82_TG1 model, record the value read on the manometer and
continue.
7. On any 64_TG1 model, if the measured pressure is
above
the specified range, command max-
imum fire (MVP = 255) and main air damper fully open (D = 0). Adjust VB until the differen-
tial pressure is within the acceptable range specified in
.
8. On any 76_TG1 or 82_TG1 model, command maximum fire (MVP = 255) and main air
damper fully open (D = 0). Attempt to adjust VB until the differential pressure is within the
acceptable range specified in
. If it is not possible to achieve the acceptable
range, see the below notice.
9. Command minimum fire (MVP = 001) and main air damper position 2 (D = 2).
10. Tighten the locking screw (item 4) on
VB
.
NOTICE:
Insufficient gas pressure.—If the differential gas pressure is below the range
given in
with the butterfly valve fully open, go no further. There is a prob-
lem with the gas supply. It will not be possible to make the subsequent adjustments.
• On any 64_TG1 model, troubleshoot then restart the adjustment steps. If the differential pres-
sure is close to the required range, you can open the ratio regulator (RR in
)
an additional amount, not to exceed 2 additional turns. On any 76_TG1 or 82_TG1 model,
contact the Milnor factory for assistance. You may need to provide the value recorded in Step
6, above.
Set the Heating System—Ratio Air Dryer
69
Содержание 6464TG1L
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 9: ...Safety 1 5 ...
Страница 31: ...Installation 2 27 ...
Страница 77: ...Installation Drawings 3 73 ...
Страница 78: ......
Страница 79: ...75 ...
Страница 80: ...76 ...
Страница 81: ...77 ...
Страница 82: ...78 ...
Страница 83: ...79 ...
Страница 84: ...80 ...
Страница 85: ...81 ...