A3.2: Check the rack number (P752) on the Milltronics device; some Allen-Bradley
PLCs can accept only a limited number of racks. Try setting the rack number to a
lower available rack number.
A3.3: Check that no other devices connected to this remote I/O link have been set to
the same rack number and starting group as the Milltronics device.
A3.4: Make sure the Milltronics device is connected and terminated correctly and in
agreement with all Allen-Bradley remote I/O wiring practices (please contact your
Allen-Bradley representative for the latest guidelines).
A3.5: Make sure the termination resistor switch on the SmartLinx module is set
correctly. Improper termination can interfere with proper remote I/O operation.
Q4:
Choosing the remote I/O Autoconfigure from my PLC programming
software doesn’t show the Milltronics device on the remote I/O link.
A4.1: Check the baud rate setting (P751) on the Milltronics device; it should match the
baud rate of the remote I/O scanner port on the PLC.
A4.2: Check the rack number (P752) on the Milltronics device; some Allen-Bradley
PLCs may accept only a limited number of racks. Try setting the rack number to
a lower available rack number.
A4.3: Try manually adding the Milltronics device to the PLC remote I/O scan list. If the
problem persists, contact Milltronics technical support.
Q5:
The Milltronics device indicates it is being scanned, but the PLC indicates
a rack fault at that address.
A5.1: Check the rack size setting (P754); make sure it matches the rack size in the
PLC’s remote I/O scan list.
Q6:
My PLC is scanning the Milltronics device with no rack faults, but the data
I’m reading makes no sense.
A6.1: Make sure the PLC is actually addressing the Milltronics device, and that no
other units are addressed to the same remote I/O rack number and starting
group. The PLC might be reading another device at the same rack number and
starting group.
A6.2: Check the information you’ve written to the discrete output area or block transfer
write area. Most of the information returned depends on what (configuration)
information was written to the Milltronics device.