TROUBLESHOOTING
==================================================================
GENERALLY…
In all cases, first check that the SmartLinx module has passed its on-going built-in self
test (device parameter P790). The result should be PASS .
If FAIL is indicated, either the module is defective, or the module connector on the
Milltronics device is defective.
If “ERR1” is indicated, the Milltronics software doesn’t recognize the ID number of the
installed module. Please contact Milltronics or your distributor for instructions and/or
upgraded Milltronics SmartLinx compatible device software.
SPECIFICALLY…
Q1:
I connected the Milltronics device to my remote I/O link. All
communications have stopped, and I have rack fault bits set on all remote
racks in the scan list.
A1.1: Make sure the Milltronics device is connected and terminated correctly and in
agreement with all Allen-Bradley remote I/O wiring practices (please contact your
Allen-Bradley representative for the latest guidelines).
A1.2: Make sure the termination resistor switch on the SmartLinx module is set
correctly. Improper termination can interfere with proper remote I/O operation.
Q2:
I connected the Milltronics device to my remote I/O link. Communication
with certain racks has stopped, and I have rack fault bits set on those
remote racks.
A2.1: Make sure the Milltronics device is connected and terminated correctly and in
agreement with all Allen-Bradley remote I/O wiring practices (please contact your
Allen-Bradley representative for the latest guidelines).
A2.2: Make sure the termination resistor switch on the SmartLinx module is set
correctly. Improper termination can interfere with proper remote I/O operation.
A2.3: Check that those remote I/O devices have different rack numbers and starting
groups from the Milltronics device.
Q3:
My PLC indicates a rack fault where the Milltronics device is addressed on
the remote I/O link, but all other devices operate properly.
A3.1: Check the baud rate, rack number, starting group, rack size and last rack
settings on the Milltronics device (P751-P755, respectively), and make sure they
match the entry in the PLC’s scan list.