TM-357 Page 7
Dynasty DX
2-7.
115 Volts AC Duplex Receptacle (Optional), Power Switch Location, and Circuit
Breaker CB1
ST-801 866-A
1
115 V 10 A AC Receptacle
2
Circuit Breaker CB1
CB1 protects the 115 volts ac du-
plex receptacle from overload.
Press button to reset breaker.
3
Power On/Off Switch
1
3
2
2-8.
Electrical Service Guide
Actual input voltage cannot exceed
±
15% of indicated required input voltage. If
actual input voltage is outside of this range, no output is available.
NOTE
Three-Phase
Single-Phase
Input Voltage
230
460
230
460
AC
26.5
17.9
62.6
32.2
Input Amperes At Rated Output
DC
20.5
13.4
44
25.8
Max Recommended Standard Fuse Or Circuit Breaker
Rating In Amperes
50
25
100
50
Min Input Conductor Size In AWG/Kcmil
10
14
8
10
Max Recommended Input Conductor Length In Feet
(Meters)
104 (32)
165 (50)
90 (27)
241 (74)
Min Grounding Conductor Size In AWG/Kcmil
10
14
8
10
Reference: 1996 National Electrical Code (NEC).
S-0092J
Содержание DYNASTY DX
Страница 27: ...TM 357 Page 25 Dynasty DX Notes...
Страница 47: ...TM 357 Page 45 Dynasty DX SD 183 036 C...
Страница 49: ...TM 357 Page 47 Dynasty DX SD 189 922...
Страница 51: ...TM 357 Page 49 Dynasty DX SD 183 037 B...
Страница 53: ...TM 357 Page 51 Dynasty DX SD 183 732 A...
Страница 55: ...TM 357 Page 53 Dynasty DX SD 183 732 A...
Страница 57: ...TM 357 Page 55 Dynasty DX SD 183 732 A...
Страница 59: ...TM 357 Page 57 Dynasty DX Notes...
Страница 61: ...TM 357 Page 59 Dynasty DX SD 189 540...
Страница 63: ...TM 357 Page 61 Dynasty DX SD 189 540...
Страница 68: ...TM 357 Page 66 Dynasty DX Notes...