OM-262 752 Page 34
5-14. Weld Output Terminals And Selecting Cable Sizes*
NOTICE − The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source is
100 ft (30 m) from the workpiece, the total cable length in the weld circuit is 200 ft (2 cables x 100 ft). Use the 200 ft (60 m) column to determine cable
size.
!
Turn off power be-
fore connecting to
weld output termi-
nals.
!
Do not use worn,
damaged, under-
sized, or repaired
cables.
Weld Output
Terminals
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit
Not Exceeding***
100 ft (30 m) or Less
150 ft
(45 m)
200 ft
(60 m)
250 ft
(70 m)
300 ft
(90 m)
350 ft
(105 m)
400 ft
(120 m)
Welding
Amperes
10 − 60%
Duty
Cycle
AWG (mm
2
)
60 − 100%
Duty
Cycle
AWG (mm
2
)
10 − 100% Duty Cycle
AWG (mm
2
)
100
4 (20)
4 (20)
4 (20)
3 (30)
2 (35)
1 (50)
1/0 (60)
1/0 (60)
150
3 (30)
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
3/0 (95)
200
3 (30)
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
4/0 (120)
250
2 (35)
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x2/0
(2x70)
300
1 (50)
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x3/0
(2x95)
350
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x3/0
(2x95)
2x4/0
(2x120)
400
1/0 (60)
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x4/0
(2x120)
2x4/0
(2x120)
500
2/0 (70)
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x4/0
(2x120)
3x3/0
(3x95)
3x3/0
(3x95)
600
3/0 (95)
4/0 (120)
2x2/0
(2x70)
2x3/0
(2x95)
2x4/0
(2x120)
3x3/0
(3x95)
3x4/0
(3x120)
3x4/0
(3x120)
700
4/0 (120)
2x2/0 (2x70)
2x3/0
(2x95)
2x4/0
(2x120)
3x3/0
(3x95)
3x4/0
(3x120)
3x4/0
(3x120)
4x4/0
(4x120)
800
4/0 (120)
2x2/0 (2x70)
2x3/0
(2x95)
2x4/0
(2x120)
3x4/0
(3x120)
3x4/0
(3x120)
4x4/0
(4x120)
4x4/0
(4x120)
*
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
( ) = mm
2
for metric use
***For distances longer than those shown in this guide, call a factory applications rep. at 920-735-4505 (Miller) or 1-800-332-3281 (Hobart).
Ref. S-0007-K 2013−09
Содержание Big Blue 800 DUO PRO
Страница 60: ...OM 262 752 Page 56 SECTION 11 ELECTRICAL DIAGRAMS Figure 11 1 Circuit Diagram For Welding Generator Part 1...
Страница 61: ...OM 262 752 Page 57 262 749 B...
Страница 62: ...OM 262 752 Page 58 Figure 11 2 Circuit Diagram For Welding Generator Part 2...
Страница 63: ...OM 262 752 Page 59 262 749 B...
Страница 85: ...OM 262 752 Page 81 Notes...
Страница 86: ...OM 262 752 Page 82 Notes...