OM-222166 Page 15
!
Installation must meet all National
and Local Codes − have only qualified
persons make this installation.
!
Disconnect and lockout/tagout input
power before connecting input con-
ductors from unit. Follow established
procedures regarding the installation
and removal of lockout/tagout de-
vices.
!
Make input power connections to the
welding power source first.
!
Always connect green or green/yel-
low conductor to supply grounding
terminal first, and never to a line ter-
minal.
.
The circuitry in this unit automatically
adapts the power source to the primary
voltage being applied. Check input volt-
age available at site. This unit can be
connected to either 460 or 575 VAC input
power.
See rating label on unit and check input volt-
age available at site.
1
Input Power Conductors (Customer
Supplied Cord)
Select size and length of conductors using
Section 5-3. Conductors must comply with
national, state, and local electrical codes. If
applicable, use lugs of proper amperage
capacity and correct hole size.
Welding Power Source Input Power Con-
nections
2
Strain Relief (Customer Supplied)
Install strain relief of proper size for unit and
conductors. Route conductors (cord)
through strain relief. Tighten strain relief.
3
Welding Power Source Grounding
Terminal
4
Green Or Green/Yellow Grounding
Conductor
Connect green or green/yellow grounding
conductor to welding power source ground-
ing terminal first.
5
Welding Power Source Line Terminals
6
Input Conductors L1, L2 And L3
Connect input conductors L1, L2 and L3 to
welding power source line terminals.
Close and secure access door on welding
power source.
Disconnect Device Input Power Connec-
tions
7
Disconnect Device (switch shown in
OFF position)
8
Disconnect Device (Supply) Grounding
Terminal
9
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1, L2, And L3 to
disconnect device line terminals.
10 Over-Current Protection
Select type and size of over-current protec-
tion using Section 5-3 (fused disconnect
switch shown).
Close and secure door on line disconnect de-
vice. Follow established lockout/tagout pro-
cedures to put unit in service.
Connecting 3-Phase Input Power For 460/575 Volt Models (continued)
input3 2015−01
Notes