OM-236 031 Page 11
3-7. Tipping
!
Do not move or operate unit
where it could tip.
956142737_5
−
5_B
3-8. Weld Output Terminals and Selecting Cable Sizes
NOTICE
−
The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source is
30 m (100 ft) from the workpiece, the total cable length in the weld circuit is 60 m (2 cables x 30 m). Use the 60 m (200 ft) column to determine cable
size.
!
Turn off power be-
fore connecting to
weld output termi-
nals.
!
Do not use worn,
damaged, under-
sized, or poorly
spliced cables.
Weld Output
Terminals
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit
Not Exceeding***
30 m (100 ft) or Less
45 m
(150 ft)
60 m
(200 ft)
70 m
(250 ft)
90 m
(300 ft)
105 m
(350 ft)
120 m
(400 ft)
Welding
Amperes
10
−
60%
Duty
Cycle
mm
2
(AWG)
60
−
100%
Duty
Cycle
mm
2
(AWG)
10
−
100% Duty Cycle
mm
2
(AWG)
Negative
Terminal
Positive
Terminal
956142737_5
−
5_B
100
20 (4)
20 (4)
20 (4)
30 (3)
35 (2)
50 (1)
60 (1/0)
60 (1/0)
150
30 (3)
30 (3)
35 (2)
50 (1)
60 (1/0)
70 (2/0)
95 (3/0)
95 (3/0)
200
30 (3)
35 (2)
50 (1)
60 (1/0)
70 (2/0)
95 (3/0)
120 (4/0)
120 (4/0)
250
35 (2)
50 (1)
60 (1/0)
70 (2/0)
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x70
(2 ea. 2/0)
300
50 (1)
60 (1/0)
70 (2/0)
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x95
(2 ea. 3/0)
2x95
(2 ea. 3/0)
350
60 (1/0)
70 (2/0)
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x95
(2 ea. 3/0)
2x95
(2 ea. 3/0)
2x120
(2 ea. 4/0)
400
60 (1/0)
70 (2/0)
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x95
(2 ea. 3/0)
2x120
(2 ea. 4/0)
2x120
(2 ea. 4/0)
500
70 (2/0)
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x95
(2 ea. 3/0)
2x120
(2 ea. 4/0)
3x95
(3 ea. 3/0)
3x95
(3 ea. 3/0)
600
95 (3/0)
120 (4/0)
2x70
(2 ea. 2/0)
2x95
(2 ea. 3/0)
2x120
(2 ea. 4/0)
3x95
(3 ea. 3/0)
3x120
(3 ea. 4/0)
3x120
(3 ea. 4/0)
*
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
**Weld cable size is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
***For distances longer than those shown in this guide, call a factory applications representative.
Milan Ref. S-0007-G 2009
−
08
Содержание STR 450
Страница 24: ...OM 236 031 Page 20 SECTION 6 ELECTRICAL DIAGRAMS Figure 6 1 Circuit Diagram For STR 450 ...
Страница 25: ...OM 236 031 Page 21 956142738 A ...
Страница 29: ...Notes Work like a Pro Pros weld and cut safely Read the safety rules at the beginning of this manual ...
Страница 30: ...Notes Work like a Pro Pros weld and cut safely Read the safety rules at the beginning of this manual ...