OM-1319 Page 13
2-10. Positioning Jumper Links
Ref. 802 553
Check input voltage available at
site.
1
Jumper Links Access Door
Open door.
2
Jumper Link Label
Check label – only one is on unit.
3
Input Voltage Jumper Links
Move jumper links to match input
voltage.
Close and secure access door.
3
Tools Needed:
2
1
230 VOLTS
460 VOLTS
575 VOLTS
S-144 916-A
3/8 in
200 VOLTS
230 VOLTS
S-153 980
2-11. Electrical Service Guide
Input Voltage
200
230
400
460
575
Input Amperes At Rated Output
50
44
25
22
18
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
60
50
30
25
20
Normal Operating
3
80
70
35
30
25
Min Input Conductor Size In AWG/Kcmil
8
10
12
14
14
Max Recommended Input Conductor Length In Feet (Meters)
93
(28)
82
(25)
152
(46)
130
(40)
204
(62)
Min Grounding Conductor Size In AWG/Kcmil
8
10
12
14
14
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
Y
Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.