OM-218 Page 20
4-11. Electrical Service Guide
Input Voltage
220
230
380
440
460
575
Input Amperes At Rated Output
178
170
103
89
85
68
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
200
200
125
110
100
80
Normal Operating
3
250
250
150
125
125
100
Min Input Conductor Size In AWG
4
3/0
2/0
2
3
3
4
Max Recommended Input Conductor Length
In Feet (Meters)
230
(70)
214
(65)
349
(106)
389
(118)
424
(129)
554
(169)
Min Grounding Conductor Size In AWG
4
4
4
6
6
6
8
Reference: 2005 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
SECTION 5
−
OPERATION
ST-144 570-A
1
Remote Amperage Control
Switch
2
Module Supplementary
Protectors (See Section 6-2)
3
Amperage Adjustment Control
4
Power Switch
5
Pilot Light
1
4
2
3
5
5-1. Controls
Содержание MARK VIII-2
Страница 4: ...Notes...
Страница 29: ...OM 218 Page 25 Notes...
Страница 30: ...OM 218 Page 26 SECTION 7 ELECTRICAL DIAGRAM Figure 7 1 Circuit Diagram For Polyweld System...
Страница 31: ...OM 218 Page 27 SD 082 527 C...
Страница 42: ...Notes...