OM-4406 Page 60
Return To Table Of Contents
11-3. Run-In Procedure Using Resistance Grid
S-0684
Stop engine.
Do not touch hot exhaust
pipe, engine parts, or load
bank/grid.
Keep exhaust and pipe away
from flammables.
Do not perform run-in
procedure at less than 20
volts weld output and do not
exceed duty cycle or equip-
ment damage may occur.
1
Resistance Grid
Use grid sized for generator rated
output.
Turn Off grid.
2
Welding Generator
Place A/V range switch in maxi-
mum position, A/V control in mini-
mum position, and Output Selector
switch (if present) in either DC
position.
3
Weld Cables
Connect grid to generator weld
output terminals using proper size
weld cables with correct connec-
tors (polarity is not important).
4
Voltmeter
5
Clamp-On Ammeter
Connect voltmeter and ammeter as
shown, if not provided on generator.
Start engine and run for several
minutes.
Set grid switches and then adjust
generator A/V control so load
equals rated voltage and current of
the generator (see nameplate, rat-
ing label, or the specifications sec-
tion in this manual).
Check generator and meters after
first five minutes then every fifteen
minutes to be sure generator is
loaded properly.
Check oil level frequently dur-
ing run-in; add oil if needed.
After one hour (minimum), place
A/V control in minimum position,
then shut down grid to remove load.
Run engine several minutes at no
load.
Stop engine and let cool.
6
Engine Exhaust Pipe
Repeat procedure if wetstacking is
present.
1
3
5
+
4
2
6
Содержание Big 40 CAT
Страница 39: ...OM 4406 Page 33 Return To Table Of Contents Notes ...
Страница 47: ...OM 4406 Page 41 Return To Table Of Contents SECTION 9 MAINTENANCE TROUBLESHOOTING 9 1 Maintenance Label ...
Страница 61: ...OM 4406 Page 55 Return To Table Of Contents 215 296 B ...
Страница 62: ...OM 4406 Page 56 Return To Table Of Contents Figure 10 2 Circuit Diagram For CC CV Welding Generator ...
Страница 63: ...OM 4406 Page 57 Return To Table Of Contents 215 297 B ...
Страница 90: ......