12-3. Grounding When Supplying Building Systems
ST-800 576-B
1
Equipment Grounding
Terminal
2
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3
Ground Device
Ground generator to system
earth ground if supplying
power to a premises (home,
shop, farm) wiring system.
GND/PE
1
2
Use ground device as stated
in electrical codes.
2
3
12-4. How Much Power Does Equipment Require?
S-0623
1
Resistive Load
A light bulb is a resistive load and
requires a constant amount of power.
2
Non-Resistive Load
Equipment with a motor is a non-re-
sistive load and requires approxi-
mately six times more power while
starting the motor than when running
(see Section 12-8).
3
Rating Data
Rating shows volts and amperes, or
watts required to run equipment.
VOLTS 115
4.5
60
AMPS
Hz
1
2
3
3
EXAMPLE 1:
If a drill uses 4.5 amperes at 115 volts, calculate its running power
requirement in watts.
4.5 A x 115 V = 520 W
The load applied by the drill is 520 watts.
EXAMPLE 2:
If three 200 watt flood lamps are used with the drill from Example 1,
add the individual loads to calculate total load.
The total load applied by the three flood lamps and drill is 1120 watts.
(200 W + 200 W + 200 W) + 520 W = 1120 W
AMPERES x VOLTS = WATTS
Содержание Big 40 C
Страница 14: ...OM 4427 Page 10 3 2 Manufacturer s Rating Labels CC Export Models CC CV Models CC Models CC CV Export Models ...
Страница 33: ...OM 4427 Page 29 Notes ...
Страница 41: ...OM 4427 Page 37 SECTION 9 MAINTENANCE TROUBLESHOOTING 9 1 Maintenance Label ...
Страница 53: ...OM 4427 Page 49 Notes ...
Страница 54: ...OM 4427 Page 50 SECTION 10 ELECTRICAL DIAGRAMS Figure 10 1 Circuit Diagram For CC Welding Generator ...
Страница 55: ...OM 4427 Page 51 223 522 B ...
Страница 56: ...OM 4427 Page 52 Figure 10 2 Circuit Diagram For CC CV Welding Generator ...
Страница 57: ...OM 4427 Page 53 223 523 B ...
Страница 88: ......