OM-4428 Page 58
SECTION 11
−
TROUBLESHOOTING
11-1. Troubleshooting
A. Welding
−
CC Models
Trouble
Remedy
No weld output; generator power output
okay at ac receptacles.
Check position of Ampere Range switch.
Check position of optional Polarity switch.
Place Amperage Adjust switch in Panel position, or place switch in Remote position and connect remote
control to Remote Amperage Adjust receptacle RC13 (see Sections 5-11 and 6-1).
Check and secure connections to Remote Amperage Adjust receptacle RC13 (see Section 5-11).
Check fuse F2, and replace if open (see Section 9-8 or 10-9). Have Factory Authorized Service Agent
check integrated rectifier SR2 and the rotor.
Have Factory Authorized Service Agent check brushes and slip rings, and weld excitation circuit.
No weld output or generator power out-
put at ac receptacles.
Disconnect equipment from generator power receptacles during start-up.
Check fuses F1 and F2, and replace if open (see Section 9-8 or 10-9). Have Factory Authorized Service
Agent check integrated rectifier SR1, capacitor C9, integrated rectifier SR2, and the rotor.
Reset supplementary protector CB12. Have Factory Authorized Service Agent check diode D1 (see Sec-
tion 9-8 or 10-9).
Have Factory Authorized Service Agent check brushes and slip rings, and field excitation circuit.
Erratic weld output.
Check and tighten connections inside and outside unit.
Be sure connection to work piece is clean and tight.
Use dry, properly stored electrodes.
Remove excessive coils from weld cables.
Have Factory Authorized Service Agent check brushes and slip rings.
High weld output.
Check engine speed, and adjust if necessary.
Have Factory Authorized Service Agent check OCV control circuit.
Low weld output.
Check engine speed, and adjust if necessary.
Check fuses F1 and F2, and replace if open (see Section 9-8 or 10-9). Have Factory Authorized Service
Agent check integrated rectifier SR1, capacitor C9, integrated rectifier SR2, and the rotor.
Electrode sticks to the workpiece more
frequently during low voltage (short arc
length) conditions.
Circuit breaker CB4 may be open. CB4 automatically resets when the fault is corrected (see Section 9-8
or 10-9). Have Factory Authorized Service Agent check transformer T1 and integrated rectifiers SR4 and
SR5.
Low open-circuit voltage.
Check engine speed, and adjust if necessary.
Maximum weld output only in each
ampere range (with Stick/TIG Selection
switch in Stick position).
Have Factory Authorized Service Agent check control relay CR7.
No remote fine amperage control.
Place Amperage Adjust switch in Remote position.
Check and secure connections to Remote Amperage Adjust receptacle RC13 (see Section 5-11).
Reset supplementary protector CB11 (see Section 9-8 or 10-9). Have Factory Authorized Service Agent
check control relay CR7.
Repair or replace remote control device.
Have Factory Authorized Service Agent check OCV control circuit.
Содержание 600 X
Страница 17: ...OM 4428 Page 13 3 2 Manufacturer s Rating Labels CC Models CC CV Models...
Страница 67: ...OM 4428 Page 63 215 221 E...
Страница 68: ...OM 4428 Page 64 Figure 12 2 Circuit Diagram For CC Welding Generator Deutz F4L2011 Powered Units Export Models...
Страница 69: ...OM 4428 Page 65 235 275 A...
Страница 70: ...OM 4428 Page 66 Figure 12 3 Circuit Diagram For CC CV Welding Generator Deutz F4L2011 Powered Units...
Страница 71: ...OM 4428 Page 67 215 806 E...
Страница 73: ...OM 4428 Page 69 235 276 A...
Страница 74: ...OM 4428 Page 70 Figure 12 5 Circuit Diagram For CC Welding Generator Deutz F3L912 Powered Units...
Страница 75: ...OM 4428 Page 71 215 807 D...
Страница 76: ...OM 4428 Page 72 Figure 12 6 Circuit Diagram For CC CV Welding Generator Deutz F3L912 Powered Units...
Страница 77: ...OM 4428 Page 73 215 808 D...
Страница 106: ......