OM-129 647 Page 45
SECTION 10
−
AUXILIARY POWER GUIDELINES
10-1. Selecting Equipment
aux_pwr 2/99
−
Ref. ST-159 730 / ST-800 577
1
Auxiliary Power Receptacles
−
Neutral Bonded To Frame
2
3-Prong Plug From Case
Grounded Equipment
3
2-Prong Plug From Double
Insulated Equipment
OR
2
Be sure equipment
has this symbol
and/or wording.
3
1
10-2. Grounding Generator To Truck Or Trailer Frame
S-0854
1
Generator Base
2
Metal Vehicle Frame
3
Equipment Grounding
Terminal
4
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
If unit does not have GFCI
receptacles, use GFCI-pro-
tected extension cord.
OR
1
2
Electrically bond generator
frame to vehicle frame by
metal-to-metal contact.
GND/PE
2
3
4