12. TECHNICAL DATA
Power Supply (DM36, DM36V)
Auxiliary supply
: Self-powered by phase voltage input
Input voltage
: 65 ~ 280 VAC
Power Supply (DM36A)
Auxiliary supply
: 65 ~ 280 VAC
Display
Display type
: White colour LED display
Display formats
: 3 rows x 4 digits per row with indicators
Measurement System
System
: Single-phase or 3-phase 4-wire system
Current Measurement (True RMS)
Measurement type
: True RMS current for L1, L2, L3
and calculated neutral current
CT primary
: 5 ~ 9999 A
CT secondary
: 5 A
Minimum current measurement
: 10 mA (CT secondary)
Accuracy
: 1.0% from 1A to 6A (secondary)
Burden
: < 0.05 VA at 5 A
Sustained overload
: 6 A
Voltage Measurement (True RMS)
Phase voltage
: 65 ~ 280 V AC
Minimum voltage measurement
: 10 V
Accuracy
: 0.5% of full scale ±1 digit
Frequency Measurement
Measurement input
: Any available voltage input
Measurement range
: 45.0 ~ 65.0 Hz
Accuracy
: 0.5%
Active Power Measurement
Measurement type
: Instantaneous active power
Accuracy :
1.0%
Power Factor Measurement
Measurement type
: True power factor and displacement power factor
Accuracy
: 1.0 degree from ±0.50 to 1.00 PF
Mechanical
Approximate weight
: 0.26 kg
Dimension (mm)
: 96(w) x 96(h) x 55(d)
Mounting
: Panel mount
Panel cut-out
: 91 x 91 mm
fl
ush mounted
Enclosure protection
: IP54 at the front panel, IP50 at the back body
Environmental Conditions
Overvoltage category
: CAT III
Operating temperature
: -10 to 55
o
C
Storage temperature
: -20 to 70
o
C
Humidity rating
: 5% to 95% RH non-condensing
Test Standards
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6,
IEC 61000-4-8, IEC 61000-4-11, IEC 61326-1, CISPR 11, IEC 60255-27
9. PROGRAMMING DATA
• Press the uu or vv button to step to the desired display screen.
• Press the uu and vv buttons simultaneously and hold for one second to enter the pro-
gramming mode. The header display will blink to indicate the meter has entered into the
programming mode.
• Press the uu button to increase the value of the setting data or the vv button to decrease
the value of the setting data.
• To save the selected value and to exit the programming mode, press the uu and vv
buttons simultaneously and hold for one second. The display will stop blinking and the
newly set data will be displayed.
• During the programming mode, if there is no button press for 15 seconds, the meter will
automatically exit the programming mode. The display will stop blinking and reset back
to its initial value.
9.1 SYSTEM SELECT
9.2 CT PRIMARY CURRENT
(DM36 and DM36A)
9.3 POWER FACTOR DISPLAY OPTION
(DM36)
.
9.4 DISPLAY MODE
10. PHASE VOLTAGE DISCONNECTION
• If any of the voltage measurement inputs is broken or disconnected, four dash bars will
appear on the corresponding phase voltage display.
11. PHASE SEQUENCE ERROR DETECTION
• L2 and L3 indicators will blink if the voltage sequence is wrongly wired.
• This feature is disabled if any of the voltage measurement inputs is broken.
• Select either single-phase or three-phase application
by pressing the or button.
• Set “3P” for three-phase application and “1P” for
single-phase application.
• The default setting is three-phase application.
• Set the CT primary value by pressing the uu or vv
button.
• The CT secondary is
fi
xed at 5A.
• The default value for CT primary is 5A.
• Set the power factor display mode by presing the
uu or vv button.
• Set “tPF” for true power factor and “dPF” for displace-
ment power factor.
• The default mode display is true power factor.
• There are two display modes available: rotational
mode or static mode.
• In rotational mode, the display screen will automatical-
ly scroll to the next display screen every 12 seconds
and rotate in a circular manner continuously. Only
measurement data is shown.
• In static mode, the display screen will stay at the latest
display screen permanently.
• By pressing the uu or vv button, set “YES” for
rotational mode and “NO” for static mode.
• The default display setting is rotational mode.
7. POWER UP LAMP TEST
• All display segments and indicators will turn on for one second during power up.
• Note that for DM36A and DM36V, only indicators corresponding to the respective mod-
els will turn on.
Figure 10: Display LEDs layout
8. DATA VIEWING
• The measurement and setting parameters can be viewed by stepping through the vari-
ous display screens.
• Press the button once to step to the previous screen.
• Press the button once to step to the next display screen.
• Tables 3 and 4 show the list of items displayed for DM36.
• The items are displayed in the same sequence as per the tables when scrolled.
Item
Type
Description
Symbols
1
Value
Phase voltage for L1, L2 and L3
V
2
Value
Line voltage for L12, L23 and L31
V
3
Value
RMS current for L1, L2 and L3
A / kA
4
Value
Computed neutral current
In
5
Value
Power factor for L1, L2, L3 (refer to section 9.3)
PF
6
Value
Active power for L1, L2, L3
W / kW
7
Value
Generator essentials
• Row 1 is total power factor for L1, L2, L3
• Row 2 is total active power for L1, L2, L3
• Row 3 is measured frequency
PF
W / kW
Hz
8
Setting
System Select (refer to section 9.1)
9
Setting
CT Primary Current (refer to section 9.2)
10
Setting
Power Factor Display (refer to section 9.3)
11
Setting
Display Mode (refer to section 9.4)
Table 3: Display for three-phase setting.
Item
Type
Description
Symbols
1
Value
Single-phase display 1
• Row 1: L1 line voltage
• Row 2: L1 line current
• Row 3: L1 line frequency
V
A / kA
Hz
2
Value
Single-phase display 2
• Row 1: L1 power factor
• Row 2: L1 active power
PF
W / kW
3~6
Setting
Same as items 8~11 in Table 3
Table 4: Display for single-phase setting.
Mikro Sdn Bhd
(423468-T)
Website: www.itmikro.com
No. 3, Jalan Anggerik Mokara 31/48,
Email: [email protected]
Seksyen 31, Kota Kemuning,
Tel : +603-55253863
40460 Shah Alam, Selangor Darul Ehsan, Malaysia
Fax : +603-55253873
Fig: 11: System setting
Fig: 12: CT primary value
setting
Fig: 13: PF display
Fig14: Display mode setting
V1.01