3. CONTENT OF BOX
Upon opening this box, you should
fi
nd the following items as shown in Table 2:
Item
Description
Quantity
1
DM36 / DM36V / DM36A digital multi-function meter
1
2
Retainer clip
2
3
This user guide
1
Table 2: Packing parts list
4. DIMENSION
Fig 2: Dimensions of meter
5. INSTALLATION GUIDE
• Cut a square hole on the panel. The recommended hole size is 91 x 91 mm.
• Insert the meter through the pre-cut hole.
• Slide the retainer clips along any two guide slots located at the four corners of the meter
until the meter is tightly secured on the panel.
• The retainer clips can be removed by lifting the tab lightly at the handle end and pulling
it backward.
Fig 3: Recommended dimensions of the panel cut-out hole and method for retainer clip
installation
6. WIRING GUIDE
• Connect the metering voltage inputs and current inputs according to the wiring schemes
shown in Fig 4 ~ Fig 9.
• The recommended wire size for voltage inputs is AWG16~22.
• The recommended wire size for current inputs is AWG12~18.
Fig 4: DM36 three-phase measurement
connection diagram.
DIGITAL MULTI-FUNCTION METERS
DM36 / DM36V / DM36A USER’S GUIDE
Fig 1: Meter layout
PRECAUTIONS
• Disconnect ALL power sources to the meter before performing installation, inspection
and maintenance.
• Please note that incorrect installation may impair the operation or even damage the me-
ter. There is no user serviceable part in the meter. Tampering with it may damage the
meter, resulting in injury and also voiding any warranty.
DISCLAIMER
• Mikro shall not be liable for errors contained herein including any incidental and/or conse-
quential damages arising from the use of this material.
• Mikro also reserves the right to vary the product from that described in this material
without prior notice.
1. GENERAL DESCRIPTION
• DM36, DM36V and DM36A are multi-function, integrated digital meters with a large, clear
LED display, complete with selection buttons.
• Measurements include voltage, current, active power, power factor & frequency.
• The meters are con
fi
gurable for both single-phase and three-phase applications.
• Both DM36 and DM36V are self-powered and no auxiliary power is required.
• Using these meters, applications using multiple conventional analogue meters, indica-
tors and selector switches may be simpli
fi
ed to just a single meter.
2. MODELS
DM36
DM36V
DM36A
Phase voltage
√
√
---
Line voltage
√
√
---
Line current
√
---
√
Neutral current (Computed current)
√
---
√
Active power
√
---
---
True power factor
√
---
---
Displacement power factor
√
---
---
Total power factor
√
---
---
Frequency
√
√
√
Table 1: Model information
Mikro logo
Model
Measurement
and indicators
display
Up button
Down button
91 mm
91 mm
Panel
Cut-out
7 mm 48 mm
89 mm
NOTE:
• The polarity marks for the CT (S1 and S2) must be adhered to as shown in the respec-
tive
fi
gures.
• Please make sure the current transformer (CT) input is shunted. Under no circum-
stances shall the CT connection be left open-circuited. Use a CT shorting block if
necessary.
Retainer
Clip
Retainer
Clip
Guide
96 mm
96 mm
Fig 8: DM36A three-phase current
measurement connection diagram.
LOAD
S1
S2
S1
S2
S1
S2
L1
L2
L3
Ln
L1 L2 L3 Ln
GND
I1
I2
I3
1
2
3
4
5
6
7
9
11
13
DM36
LOAD
S1
S2
S1
S2
S1
S2
L
N
L1 L2 L3 Ln
GND
I1
I2
I3
1
2
3
4
5
6
11
13
DM36A
Fig 5: DM36 single-phase measurement
connection diagram.
LOAD
L1
L2
L3
Ln
L1 L2 L3 Ln
7
9
11
13
DM36V
Fig 9: DM36A single-phase current
measurement connection diagram.
Fig 6: DM36V three-phase voltage
measurement connection diagram.
Fig 7: DM36V single-phase voltage
measurement connection diagram.
LOAD
L
N
L N
7
13
DM36V
LOAD
S1
S2
L
N
L N
GND
I1
1
2
11
13
DM36A
6.1 DM36 CONNECTION DIAGRAM
LOAD
S1
S2
L
N
L N
GND
I1
1
2
7
13
DM36
6.2 DM36V CONNECTION DIAGRAM
6.3 DM36A CONNECTION DIAGRAM
AUX
AUX