DC GFP (Ground Fault Protection) 

The Classic has internal ground fault protection (GFP) built in. Since 2008, the NEC requires a DC-GFP 
on all PV systems in the USA. The built in DC-GFP eliminates the need to purchase and install an external 
DC-GFP. If the internal grounding jumper is installed in a Classic, the battery negative and DC source 
negative must not be connected to the system grounding conductor anywhere in the system. Grounding of 
these circuits will defeat the GFP function. In a network with multiple Classics connected in Follow Me, 
only one Classic should have its internal grounding jumper installed and all should have GFP enabled. The 
factory setting will make a DC negative to System Ground connection in the Classic charge controller. 
The GFP function will need to be disabled for Positive ground or an ungrounded DC system. 
 

  
                               

 

                                                                                                               

Figure 12 

 
 
The Ground fault device is simple to understand and use. It detects a fault between battery/PV negative 
and earth ground just like the breaker DC-GFP system. The difference with the Classic is that it turns off 
the charge ability and sounds a loud warning when a ground fault is detected. The Classic’s system 
consists of a PTC that is between the Negative and Ground internally in the Classic. A PTC is basically a 
self-healing fuse that will open when current exceeds its rating and reclose when current is dropped below 
its rating. The Classic will monitor this PTC and disable the charging when it senses it go open. When the 
fault is cleared the Classic will restore charging.  
 
 
To disable the internal Ground Fault Protection function, the jumper labeled GFP needs to be removed and 
the GFP function needs to be disabled in the TWEAKS menu. See “Disabling GFP” for instructions.

 

 

To reset the internal GFP function after detection has occurred: fix the actual ground fault, then turn OFF 
the Classic and turn it back ON. Do this by turning the external battery breaker to OFF position and then 
to ON position.  

Figure 11

 

Содержание Classic 150-SL

Страница 1: ...e Classic will not survive MidNite does not recommend the use of Tigo Module Optimizers with the Classic If Tigo modules must be installed Legacy P O MUST be used When the Classic is used with Wind or...

Страница 2: ...erters or charge controllers can occur Take a single XW E Panel for example it has a positive bus bar for Charge controller battery side connections This bus bar is sufficient for 2 charge controllers...

Страница 3: ...Classic SL owner s manual REV E 2056 3 P a g e 1 0 0 0 1 3 R E V E This Manual covers models Classic 150 SL 200 SL 250 SL...

Страница 4: ...to the accuracy sufficiency or suitability of any technical or other information provided in its manuals or other documentation b Assumes no responsibility or liability for loss or damage whether dire...

Страница 5: ...Mechanical 36 Classic Breaker sizing 37 Scope This Manual provides safety guidelines and installation information for the Classic SL charge controller It does not provide brand specific information a...

Страница 6: ...ctions must be kept separate from the grounding conductor connections The equipment ground terminal inside the Classic must be connected to Earth Ground for the internal DC GFP to work With the except...

Страница 7: ...ttery manufacturer for details WARNING PERSONAL PRECAUTIONS DURING INSTALLATION WARNING BATTERIES PRESENT RISK OF ELECTRICAL SHOCK BURN FROM HIGH SHORT CIRCUIT CURRENT FIRE OR EXPLOSION FROM VENTED GA...

Страница 8: ...Classic SL owner s manual REV E 2056 8 P a g e 1 0 0 0 1 3 R E V E Classic SL Power Graphs Sizing the Solar Array Table 1 Table 2 Table 3...

Страница 9: ...ller needs to have the open circuit voltage of the array about 30 higher than the highest battery voltage you plan to charge to NOTE You can find the Classic string sizing tool on the web page www mid...

Страница 10: ...screened Parts bag with stickers Terminal block cover and silicone grease User s manual printed Email customerservice midnitesolar com for more information or if anything is missing or damaged Figure...

Страница 11: ...cover in place See Figure 2 Do not force the cover if it does not seat into place easily stop and look for any cables or wires that may be interfering With the cover seated in place install the four...

Страница 12: ...and 2 plastic bushings are included with each E Panel One locknut acts as a spacer Carefully hang the Classic on the screw in the bracket and slide it over the close nipple see figure 4 Install the l...

Страница 13: ...ng the Classic front cover ALWAYS use proper Over current devices and disconnects on the PV and Battery at the Classic MidNite DC breakers work well for both WARNING to comply with Australian New Zeal...

Страница 14: ...on the DC terminal connector big blue terminal connector are Up to 10 AWG torque to 25 35 inch pounds 8 AWG torque to 30 40 inch pounds 6 AWG or above Torque to 40 50 inch pounds HyperVOC HyperVOC is...

Страница 15: ...battery cable to this bus bar 22 Earth Ground Bus Bar This is the common Earth Ground bus bar where all the grounds get wired back to and it needs to be connected to the building s ground rod system 2...

Страница 16: ...Classic SL owner s manual REV E 2056 16 P a g e 1 0 0 0 1 3 R E V E Diagram 1...

Страница 17: ...he parts bag Maximum and Minimum Wire Size The Classic s Blue DC terminal connector will accept wire from 14 4 AWG The Classic s Aux 1 and 2 terminal connector will accept wire up to 18 AWG WARNING Ex...

Страница 18: ...late rating in extreme situations so the safe minimum wire size should be selected for the PV array maximum short circuit current Please consult PV manufacturer for specifications The US National Elec...

Страница 19: ...k of injury charge only properly rated such as 6 V 12 V and 24 V lead acid GEL AGM Flooded or Nickel Cadmium rechargeable batteries Other battery types may burst causing personal injury and damage WAR...

Страница 20: ...Classic SL owner s manual REV E 2056 20 P a g e 1 0 0 0 1 3 R E V E Figure 8 Insert BTS to the jack labeled BATTERY TEMP on the control board Figure 9...

Страница 21: ...ical connection compartment Figure 10 DC System Grounding The Classic charge controller is designed to work with Negative Ground Positive Ground or Ungrounded power systems In grounded systems dc nega...

Страница 22: ...12 The Ground fault device is simple to understand and use It detects a fault between battery PV negative and earth ground just like the breaker DC GFP system The difference with the Classic is that i...

Страница 23: ...e the Quick Set Equalization To do a manual Equalization charge go into the Charge menu and highlight EQ and press Enter Now EQ Stopped will be highlighted Scroll up to select Eq Started Press the Sta...

Страница 24: ...the bottom right corner of the display then the Mode may have been turned off To turn the mode back ON push the Main Menu button several times until Charge is highlighted Scroll to the right until Mo...

Страница 25: ...he Enter Button Press the right arrow key to highlight the Out Amps column Use the up and down arrow keys to change the current limit then press the Enter Button to save this data Calibrating Battery...

Страница 26: ...if the power source goes off It has two settings that are user adjustable Sweep Interval is the time between mini sweeps in minutes and sweeps around the present i e the last found MPP Voltage The ran...

Страница 27: ...LL settings Turn the PV breaker and Battery breaker off What you don t have a breaker Get one asap and make sure the display has gone dark Do a hardware factory restore There are 4 sets of jumpers dir...

Страница 28: ...the PV positive and negative on the blue terminal block inside the Classic If the system has been running all along and this just happened call customer service The Display is showing all 0s and or G...

Страница 29: ...e Classic up Count to 4 before turning the breaker on If you do not have a breaker or disconnect and you are trying to connect a wire to a terminal block or a battery the connection will likely be to...

Страница 30: ...because it has reached the current limit you have set in the Charge menu under limits or because it is to hot and it is backing its current down to prevent overheating Go into the Main menu and the C...

Страница 31: ...en or I don t see all the settings shown in the manual If the WBjr status menu is not present or does not match the manual then you most likely have older firmware We recommend updating the firmware a...

Страница 32: ...c Lite powered on Now you can change the network settings on the Local App if you want Note setting switches to custom first and then powering the Classic Lite can cause issues trying to connect as it...

Страница 33: ...ll 6 pins inside the jack Carefully so as not to bend the pins the fans should all start spinning How do I find the Wizard You won t we removed the wizard as it asked a lot of questions that did nothi...

Страница 34: ...o the right of this it will say the battery voltage it is programmed to Example 48v I have Aux1 programmed properly but I cannot get 12v out of it when I should Most likely the Jumpers on the bottom l...

Страница 35: ...t 24v battery 65a at 48v battery 60a at 12v battery 62a at 24v battery 55a at 48v battery De rate current at 40 C 80 amperes 66 amperes 52 amperes Environment 40c to 40c Dimensions of Classic 14 87 X...

Страница 36: ...Classic SL owner s manual REV E 2056 36 P a g e 1 0 0 0 1 3 R E V E Specifications Mechanical Figure 13...

Страница 37: ...Classic SL owner s manual REV E 2056 37 P a g e 1 0 0 0 1 3 R E V E Classic Breaker sizing Table 7...

Страница 38: ...Classic SL owner s manual REV E 2056 38 P a g e 1 0 0 0 1 3 R E V E...

Страница 39: ...Classic SL owner s manual REV E 2056 39 P a g e 1 0 0 0 1 3 R E V E...

Страница 40: ...Classic SL owner s manual REV E 2056 40 P a g e 1 0 0 0 1 3 R E V E...

Страница 41: ...Classic SL owner s manual REV E 2056 41 P a g e 1 0 0 0 1 3 R E V E Table 8...

Страница 42: ...Float Constant voltage charge stage with a lower voltage than the Absorb charge point The controller is regulating so maximum power will not be seen at this time Float MPPT Maximum current charge sta...

Страница 43: ...erature sensor to measure the ambient temperature of the battery bank and will adjust the voltage set points up or down accordingly to ensure a full battery There are 3 parameters to set Minimum and M...

Отзывы: