MidNite Solar Hawke's Bay Скачать руководство пользователя страница 23

Hawke’s Bay

 Manual

 

 
 

23| P a g e                                                                                             1 0 - 4 2 5 - 1         R E V : -       F W :   X X X  

 

 

 

FET (Field Effect Transistor) temperature reaches 75C, the 

Hawke’s Bay

 will reduce its 

current output on a sliding scale relative to the FET temperature.  Or when the current-limit 
setpoint is reached, the controller will reduce its current output.  

 

DC Input Modes 

 

Solar - 

This mode is for PV systems and has a fast sweep (typically 1/2 second or less) that 

will re-sweep at user-adjustable sweep intervals, unless the Hawke’s Bay finds that it needs 
to do a sweep on its own because of changing conditions.  The timed sweep interval is user-
adjustable and is in units of minutes.

 

 

 

 

ADVANCED SETTINGS & CONCEPTS 

 

Charge Time - 

For the Absorb timer, use 

… 

Charge Time = 0.42 X (Bank Ah / Charge rate).   

EXAMPLE: 

1.

 

Your battery bank total amp-hour capacity is 400Ah 

2.

 

Your  charge  controller  outputs  65A  (This  is  based  on  PV  wattage  /  nominal  bank 
voltage) 

3.

 

Charge Time = 0.42 x (400 Ah / 65A) = 0.42 x 6.15 hours = 2.6 hours. 

For the EQ timer, refer to your battery manufacturer specifications. 

 

Temperature Compensation (T-comp) - 

There is only one setting in the 

Hawke’s Bay

 that 

can influence a different voltage than what you programmed (i.e., Absorb, Float, or EQ) and 
that is temperature compensation.  As a battery gets colder than 25 degrees Celsius, the 
charging voltage needs to be elevated.  As a battery gets warmer than 25C, the charging 
voltage needs to be lowered.  Check with your battery manufacturer and get the following 
three values:  

1.

 

Millivolts per degree C per cell to compensate (Default is -5mv).   

2.

 

Reference temperature for the battery (Default is 25C).  

3.

 

The maximum voltage to ever compensate to.  

Temperature  Offset = Number  of  cells  x  T-comp  setting  (Usually  -5mv)  x  offset  in degrees 
Celsius from the reference (Typically 25C). 

 

Ending Amps - 

Used in conjunction with the MidNite Whiz Bang Jr current-sensing device.  

Ending amps is set by the battery manufacturer and means the point at which the battery 
bank is full.  During the Absorb charge cycle, the charge controller holds the voltage at the 
preset charge level, say 58.8V.  As the batteries fill up, the current into the batteries 
decreases.  When the decreasing current drops below the preset End Amps point for 90 
seconds, the charge controller stops the Absorb cycle and transitions to Float.  In the 

Содержание Hawke's Bay

Страница 1: ...e 1 0 4 2 5 1 R E V F W X X X MidNite Solar Hawke s Bay Owner s Manual This entire manual is printed without color but is available for download with many of the diagrams available in color on our we...

Страница 2: ...rc Fault 14 Ground Fault 15 Rapid Shutdown System 15 Battery Temperature Sensor 16 Whiz Bang Jr 17 Battery Sense Circuit 18 Hawke s Bay Wiring 18 Energizing the Hawke s Bay 19 Operation 20 System and...

Страница 3: ...90A or 120A of charging current Installed Options Board for o Arc Fault Protection UL1699B o Ground Fault Protection NEC2020 o SunSpec compliant Rapid Shutdown Transmitter Compatible with flooded lead...

Страница 4: ...y read all instructions and cautionary markings The installation instructions are for use by qualified personnel only Do not perform any installation other than that specified in this manual unless yo...

Страница 5: ...torque values Use only copper wires with a minimum temperature rating of 90 C There are no user serviceable parts contained in the Hawke s Bay Always verify proper wiring prior to energizing the Hawk...

Страница 6: ...h currents if short circuited e g dropping a metal tool across the battery terminal which could cause a fire or explosion To prevent a spark at the battery and to reduce the chance of explosion turn o...

Страница 7: ...EXACTLY the same Any variance in resistance on one string versus another will cause an imbalance and the batteries will suffer a shortened lifespan Trusting a State of Charge SOC meter which can lose...

Страница 8: ...erformed by qualified personnel such as a licensed electrician DC over current protection must be provided as part of the installation Use only copper wires with a minimum temperature rating of 90 C T...

Страница 9: ...dius and do not become kinked Follow existing wire runs where possible Ensure both DC cables pass through the same knockout and conduit to allow the inductive currents to cancel All wiring to the batt...

Страница 10: ...a GF condition exists Protecting Wire Hawke s Bay Breaker Box MNHAWKES BAY BB125 DC wires to and from the Hawke s Bay must be protected as required by code This can be done by using jacketed wires or...

Страница 11: ...he wall The Hawke s Bay may be located anywhere within this 30 The NEC also requires 36 free and clear of obstructions in front of the charge controller The 36 clear area in front of all electrical pa...

Страница 12: ...op two x 2 lag bolts to wall leaving about exposed 4 Align mounting flange keyhole of Hawke s Bay Figure 1 to the lag bolts slide Hawke s Bay down 5 Install bottom lag bolts 6 Tighten lag bolts HAWKE...

Страница 13: ...on Board installed in the Hawke s Bay Figure 5 shows the Options Board sub boards and connection receptacles Bypass Switch TB1 Figure 5 For Rapid Shutdown System operations the Hawke s Bay via the Opt...

Страница 14: ...In the event the Hawke s Bay detects an AF the charge controller will shut down with audible and visual AF indications The AF issue must be remedied before the controller can resume operations Clear...

Страница 15: ...ure 10 2 Connect GF toroid to Options Board 3 Pass PV AND PV cables through GF toroid Figure 11 Activating Ground Fault 1 Go to MPPT Config then to External Sensors 2 Go to GF then ENABLE Rapid Shutdo...

Страница 16: ...rature Program the reference temperature as provided by the battery manufacturer 25C is a common reference temperature Program the temperature coefficient factor as provided by the battery manufacture...

Страница 17: ...ure 16 The wire marked Cable to Inverter Negative shows the shunt connection point for ALL negative wires from charge controllers inverter wind turbine negative and even a battery charger running off...

Страница 18: ...system will automatically use this voltage versus the voltage on the high current connections the Hawke s Bay s actual battery cables Only one Battery Sense wire connection to the battery bank is requ...

Страница 19: ...inside the Hawke s Bay o Battery bank voltage present Yes Good 29 65VDC is good No Check DC wiring to the battery Check batteries Close the Hawke s Bay Battery breaker Voltmeter Measure for battery ba...

Страница 20: ...vice Hawke s Bay o 2 Naming the system One MNGP2 can control multiple CANBUS devices such as the Hawke s Bay the Barcelona and the Rosie inverter charger Therefore one MNGP2 can look at each device by...

Страница 21: ...es disconnected Voc is the voltage you will measure with a multimeter Voc exists with daylight Voc is a function of light illuminating the PV module When Voc is maximum current flow is zero Vmp Maximu...

Страница 22: ...he internal resistance of the battery cells During the EQ cycle the Hawke s Bay applies to the battery bank an elevated charge voltage which is needed to remove sulfates from the battery s lead plates...

Страница 23: ...on T comp There is only one setting in the Hawke s Bay that can influence a different voltage than what you programmed i e Absorb Float or EQ and that is temperature compensation As a battery gets col...

Страница 24: ...charging voltage allowed Adjust if cold battery temp comp increases battery charging voltage to point that the inverter shuts down from HI BATT If so lower the Max T Comp Voltage so the inverter stays...

Страница 25: ...et batts rest measure the specific gravity of every cell EQ until the cells are at or less than 0 025 S G apart Rebulk Battery voltage setpoint below Float that once reached causes the Hawke s Bay to...

Страница 26: ...ycle Be mindful of an elevated batt bank voltage in the winter when equalizing This high batt voltage may exceed the DC IN voltage limit on some inverters Max DC IN for the Hawke s Bay is 65V Temp Com...

Страница 27: ...Name Assign custom name to Hawke s Bay Reset to Defaults Performs a factory restore USER System Functions o EQ Start Stop o Force Float Force Now o Force Bulk Force Now o DC Charge Stop start system c...

Страница 28: ...n be pulse modulated if that type of varying output is desired Certain AUX modes allow a start delay and off delay timer if it is desired to hold the start function for a period of time or to prevent...

Страница 29: ...e Test Y N ON Manual ON Manual OFF PV V on Low Y N OFF PV V Timer till OFF PV V Timer till ON PV V on High Y N ON PV V Timer till ON PV V Timer till OFF Waste Not Low Y N OFF X X V Timer till OFF X X...

Страница 30: ...FW app will appear as shown in Figure 18 5 Tap the label that reads MNGP2 6 The FW app will connect to the Hawke s Bay then the app will appear as shown in Figure 19 7 Tap the box that reads MNGP2 Sta...

Страница 31: ...nternal bypass diodes Defective module PV connectors Defective installation of PV connectors Poor crimping of the terminal PV connector not plugged in all the way A wire shorting out intermittently Pi...

Страница 32: ...irectly from the PV wires Is voltage present If not see PV INPUT ISSUE section above If voltage is present reconnect the PV wires to the Hawke s Bay s terminal block Be mindful of polarity and always...

Страница 33: ...F alert Arc Fault An arc fault is a short which produces an electrical spark arc An arc fault may occur on the PV source circuit or even on the battery side of the Hawke s Bay No AF testing is require...

Страница 34: ...Hawke s Bay Manual 34 P a g e 1 0 4 2 5 1 R E V F W X X X...

Страница 35: ...Hawke s Bay Manual 35 P a g e 1 0 4 2 5 1 R E V F W X X X...

Страница 36: ...Hawke s Bay Manual 36 P a g e 1 0 4 2 5 1 R E V F W X X X...

Страница 37: ...uthorization RA number issued by MidNite Solar For an RMA number contact MidNite Solar Inc 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any defective MidNite So...

Страница 38: ...quired to do so by prior arrangement DISCLAIMER Unless specifically agreed to in writing MidNite Solar Inc a Makes no warranty as to the accuracy sufficiency or suitability of any technical or other i...

Страница 39: ...tor Ambient Temp F 24 to 20 1 02 76 to 68 19 to 15 1 04 67 to 59 14 to 10 1 06 58 to 50 9 to 5 1 08 49 to 41 4 to 0 1 10 40 to 32 1 to 5 1 12 31 to 23 6 to 10 1 14 22 to 14 11 to 15 1 16 13 to 5 16 to...

Отзывы: