GD Midea Refrigerant Equipment Co. Ltd Service manual for Electrolux split Series
6
Typical installation
CAUTIONS:
1. Ensure that the space around the left and
right of the indoor unit is more than 12cm.
2. The indoor unit should be installed allowing a
minimum clearance of 15cm from the ceiling.
3. Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
4. For optimum performance the Indoor Unit
should be installed on the wall in areas where
the height from the floor to the ceiling is not
more than 2.3 meters.
5. A minimum pipe run of 3 meters is required to
minimize vibration & excessive noise.
6. The indoor unit should be installed on the wall
at a height of 1.7 meters or more from the
floor but less than 2.3 meters from the floor.
7. Directions A, B and C should be free from
obstructions.
2.3 INSTALLATION OF INDOOR UNIT AND
OUTDOOR
2.3.1 Indoor unit
●
Do not expose the indoor unit to heat or
steam.
●
Select a place where there are no obstacles in
front or around the unit.
●
Make sure that condensation drainage can be
conveniently routed away.
●
Do not install near a doorway.
●
Ensure that the space on the left and right of
the unit is more than 12cm.
●
Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
●
For optimum performance the indoor unit
should be installed on the wall in areas where the
height from the floor to the ceiling is not more than
2.3 meters.
●
A minimum pipe run of 3 meters is required to
minimize vibration & excessive noise.
●
The indoor unit should be installed on the wall
at a height of 1.7 meters or more from the floor but
less than 2.3 meters from the floor.
●
The indoor unit should be installed allowing a
minimum clearance of 15cm from the ceiling.
●
Any variations in pipe length will/may require
adjustment to refrigerant charge (Refer to item
2.3.3).
More th an 1.7m
Less than 2.3m
More th an 1 5cm
Mo re tha n 12cm
Mo re than 12cm
2.3.2 Outdoor unit
●
If an awning is built over the outdoor unit to
prevent direct sunlight or rain exposure, make
sure that heat radiation from the condenser is not
restricted.