V6R VRF 50/60Hz
135
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
2.24
P9, H9: Fan module protection
Digital display output
Description
Fan module protection.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition:
For P9 protection: Fan speed is too low.
For H9 protection: P9 protection appears ten times in 120 minutes.
Recover condition: Fan speed go back to normal.
Reset method:
For P9 protection: Resume automatically;
For H9 protection: Manually restart.
Possible causes
Switch ENC2 incorrectly set.
Power or communication wires not connected properly.
Fan motor blocked or has failed.
Power supply abnormal.
Fan module damaged.
Outdoor main PCB damaged.