138 Troubleshooting
4.2 E1: Phase sequence error
The error will only display on the faulty unit, all the ODUs will be on standby.
Note:
If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current
difference between C phase and A, B phase will be very large as the power supply load of each outdoor unit is on C phase, this
can easily lead to tripped breakers and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence
should be staggered, so that the current can be distributed among the three phases equally.
E1: Phase sequence error
The 3-phase sequence of power supply
is
wrong. (The A, B, C terminal of three-phase
power supply should meet compressor phase
sequence requirements. If the phase
sequence is inverted, the compressor will
operate inversely.
Exchange any two of the 3
phase sequence
Some power supply terminals are loose, if
this occurs, the compressor will operate
abnormally, and the current is very large
Ensure all supply terminals are
securely fastened
Outdoor main PCB is damaged
Replace the outdoor main PCB
No
No
Yes
Yes
The power voltage supply is abnormal, or the
neutral line and live line are connected in
reverse
Check the power supply
equipment and adjust the
power supply wiring.
Yes
No