Service manual
- 28 -
TE5
T
EVAP. temp. up
EVAP. temp. down
TE6
Compressor and
outdoor fan on
Compressor and outdoor
fan off (after 5 mins)
Condenser high temperature protection (only for heat pump)
10.7 Dehumidifying mode
Indoor fan speed at low speed.
Protection is same as cooling mode.
10.8 Heating mode
10.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way
valve must delay 2 minutes compared with compressor if the compressor changed into non-heating
mode or turned off. 4-way valve doesn't delay in dehumidifying mode
10.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost
10.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
* This parameter can be changed from 0 to 3
10.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
Содержание MSG-24CRN2
Страница 1: ...MSG 24CRN2 MSG 24HRN2 MSG 30CRN2 MSG 30HRN2...
Страница 2: ......
Страница 13: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Страница 15: ...Service manual 11 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Страница 16: ...Service manual 12 7 2 Wiring diagram 7 2 1 Cooling mode MSG 24CR MSG 30CR...
Страница 17: ...Service manual 13 7 2 2 Heating mode MSG 24HR MSG 30HR A1 A2...
Страница 18: ...Service manual 14 7 2 3 Cooling mode 3 Ph MSG 30CR 3ph...
Страница 19: ...Service manual 15 7 2 4 Heating mode 3 Ph MSG 30HR 3ph 1 7 3 4 5 6 2...