Service manual
- 23 -
8.7 Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge
indicates 0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is
higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the
case, it will not be necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be
discharged.
Содержание MSG-07CRN2
Страница 2: ......
Страница 15: ...Service manual 11 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Страница 17: ...Service manual 13 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Страница 21: ...Service manual 17 7 2 2 MSG 07HR MSG 09HR MSG 12HR...
Страница 22: ...Service manual 18 MSG 16HR MSG 18HR MSG 21HR...