29
9.7.7 Outdoor unit current control in heating mode.
1)
The frequency descending is based on current grade, and judges if descending
again or resuming every 2 minutes.
2)
If the current descends and stays at frequency remaining zone for 3 minutes, the
frequency will rise a grade. After 3 minutes if stays at this zone still, the frequency will rise a grade again.
9.7.8 Indoor heat exchanger high temperature protection.
1) If
T2
>
TEH2
℃
, compressor frequency will be descended one grade every 20 seconds. When it drops to F2, if
T2 is still higher than
TEH2
℃
and remains 3 minutes, the compressor will stop.
2)
If T2 descends to be lower than 48
℃
, or remains between 48
℃
to
TEH2
℃
for 6 minutes, frequency limit will
be released.
3) If
T2
>
60
℃
, the compressor will stop and not resume until T2
<
48
℃
.
9.7.9 Defrosting mode.
1) Condition of defrosting.
Condition 1.
If T4
>
0
℃
,
When the units are running, if the following two items are satisfied the units start defrosting:
a) The units runs with T3
<
3
℃
for 40 minutes and T3 keeps lower than
TCDI
℃
for more than 3 minutes.
b) The units runs with T3
<
3
℃
for 80 minutes and T3 keeps lower than (
TCDI
+2)
℃
for more than 3
minutes.
Remark: The above means that when T3 is lower than 3
℃
PCB begins to time, if T3 is lower than start
temperature for 3 minutes, the machine starts defrosting. Here start temperature are
TCDI
℃
and
(
TCDI
+2)
℃
.
Condition 2.
If T4
<
0
℃
,
The program judges according to the condition 1, if the two items are satisfied, then judges if T2 has descended
for more than 5
℃
, if it has the machine starts defrosting, or continues to judge T2 and will not defrost until T2
I3HEAT
I2HEAT
I1HEAT
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
out
door unit
curr
ent
Remark:
Δ
Tcon can be changed among 0, -2,- 4 , the default is 0
℃
℃
A
Δ
Th=(ro
om temp
) – (s
etti
ng
Te
m
p
) –
Δ
Tc
on
5.0
4.5
3.5
3.0
2.5
2.0
1.5
1.0
0.5
H
G
F
E
D
C
B
℃
Содержание MSC-09HRDN1-QD0(E)
Страница 8: ...5 3 Dimension 3 1 Indoor Unit MSC 09HRDN1 QD0 E MSC 12HRDN1 QC6 E MSH 09HRDN1 QD0 E MSH 12HRDN1 QC6 E...
Страница 9: ...6 3 2 Outdoor Unit MOC 09HDN1 QD0 E MOC 12HDN1 QC6 E...
Страница 12: ...9 5 Refrigerant cycle diagram...
Страница 13: ...10 6 Wiring diagram 6 1 Indoor Unit MSC 09HRDN1 QD0 E MSC 12HRDN1 QC6 E MSH 09HRDN1 QD0 E MSH 12HRDN1 QC6 E...
Страница 14: ...11 6 2 Outdoor Unit MOC 09HDN1 QD0 E MOC 12HDN1 QC6 E...