35
In drying mode, if room temperature is lower than 10
℃
, com presso
temperature exceeds 12
℃
.
8.4.5.4 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are valid, and they are the same as that in cooling mode.
8.4.5.5 The outdoor fan operates same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
Pressing the touch button once, the machine will transfer into forced auto mode, if pressing the button
once again, the machine will turn into forced cooling mode, the third pressing will stop the unit, and the
forth pressing is the start of the cycle of forced auto mode, forced cooling mode and stop. Refer the
following chart:
8.4.6.2 In forced operation mode, all general protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the
machine will turn to auto mode as 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24
℃
setting tem peratu
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours, and the minimum resolution is 15 minutes.
8.4.7.2 Timer on. After turning off, the machine will turn on automatically when reaching the setting
time.
8.4.7.3 Timer off. After turning on, the machine will turn off automatically when reaching the setting
time.
8.4.7.4 Timer on/off. After turning off, the machine will turn on automatically when reaching the
setting “on” time, and then turn off automatically when reaching the setting “off” time.
8.4.7.5 Timer off/on. After turning on, the machine will turn off automatically when reaching the