Basic test procedure 

24

 

ƒ

 

Restart unit several times after allowing pressures to stabilize. Pinch off process tubes, 

cut and solder the ends. Remove pinch off tool, and leak check the process tube ends. 

 
 

9.2.4  Special procedure in the case of compressor motor burnout. 

ƒ

 

Recover all refrigerant and oil from the system. 

ƒ

 

Remove compressor, capillary tube and filter drier from the system. 

ƒ

 

Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent, to 

remove all contamination from system. Inspect suction and discharge line for carbon deposits. 
Remove and clean if necessary. 

ƒ

 

Reassemble the system, including new drier strainer and capillary tube. 

ƒ

 

Proceed with processing as outlined under hermetic component replacement. 

 

9.2.5  Rotary compressor special troubleshooting and service 

Basically, troubleshooting and servicing rotary compressors is the same as on the 
reciprocating compressor with only a few exceptions. 

ƒ

 

Because of the spinning motion of the rotary, the mounts are critical. If vibration is 

present, check the mounts carefully. 

ƒ

 

The electrical terminals on the rotary are in a different order than the reciprocating 

compressors. The terminal markings are on the cover gasket. Use your wiring diagram to 
insure correct connections. 

 

9.2.6 Refrigerant 

charge 

ƒ

 

The refrigerant charge is extremely critical. It must be measured charge carefully - as 

exact as possible to the nameplate charge. 

ƒ

 

The correct method for charging the rotary is to introduce liquid refrigerant into the high 

side of the system with the unit off. Then start compressor and enter the balance of the 
charge, gas only, into the low side. 

The introduction of liquid into the low side, without the use of a capillary tube, will cause 
damage to the discharge valve of the rotary compressor. 
NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged 
with the plugs from the replacement compressor. 
 

9.3 Fan 

motor 

A single phase permanent split capacitor motor is used to drive the evaporator blower and 
condenser fan. A self-resetting overload is located inside the motor to protect against high 
temperature and high amperage conditions. 
 

9.3.1  Fan motor test 

ƒ

 

Determine that capacitor is serviceable. 

ƒ

 

Disconnect fan motor wires from fan speed switch or system switch. 

ƒ

 

Apply "live" test cord probes on black wire and common terminal of capacitor. Motor 

should run at high speed. 

ƒ

 

Apply "live" test cord probes on red wire and common terminal of capacitor. Motor should 

run at low speed. 

Содержание MPM1-10CEN1-BB6

Страница 1: ...Portable air conditioner MPM1 10CEN1 BB6 MPM1 10EEN1 BB6 MPM1 10CRN1 BB6 MPM1 10ERN1 BB6...

Страница 2: ...Permanent installation 12 7 Feature 14 8 Electronic function 15 8 1 Terms and definitions 15 8 2 Electric part assembly condition that use 15 8 3 PCB working environment 15 8 4 Protection function 16...

Страница 3: ...ect the power supply plug or turn off the breaker 1 2 Caution Always check for gas refrigerant leakage after installation or repair of product Install the drain hose to ensure that water is drained aw...

Страница 4: ...pe Do not mix old and mew batteries or different types of batteries Do not recharge or disassemble the batteries Do not dispose of batteries in a fire If the liquid from the batteries gets onto your s...

Страница 5: ...g W H D mm 725 875 460 725 875 460 Net Gross weight Kg 40 52 40 52 Applicable ambient Operation temp 17 30 17 30 Ambient temp 10 35 35 Application area m2 14 21 14 21 Water Pump 1 and 2 Current mA 40...

Страница 6: ...Number of circuits 2 2 Cond a Number of rows 2 2 b Tube pitch a x row pitch b mm 21X13 37 21X13 37 c Fin spacing mm 1 3 1 3 d Fin type code Hydrophilic aluminum Hydrophilic aluminum e Tube outside di...

Страница 7: ...Outer dimension 5 3 Out dimension...

Страница 8: ...External view part display 6 4 Display 4 1 LED display 4 2 LCD display...

Страница 9: ...Refrigerant cycle diagram 7 5 Refrigerant cycle diagram The figure below is a brief description of the important components and their function in what is called the refrigeration system...

Страница 10: ...Installation detail 8 6 PCB drawing wiring diagram 6 1 10K Model The below picture is fit for MPM1 10CEN1 BB6 MPM1 10CRN1 BB6 MPM1 10EEN1 BB6 MPM1 10ERN1 BB6...

Страница 11: ...d be kept The appliance shall not be used in the washroom The plug shall accessible after appliance is positioned Wiring shall be done according to National rules Please see the picture show as below...

Страница 12: ...djustable panel if the width of window is less than 26 Open the window sash and place the window panel on the window stool Secure the window panel to the window stool with 2 screws 6 4 3 Cut the foam...

Страница 13: ...Adjust the length of the sliding window panel according to the width of window short the adjustable panel if the width of window is less than 26 Open the sliding sash and place the window panel on the...

Страница 14: ...ter window sash Show as below picture 6 6 Permanent installation 6 6 1 Attach one end of the duct to the exhaust air outlet of the mobile air conditioner According to the arrow direction push it downw...

Страница 15: ...Installation detail 13 6 6 4 Cover the hole using the adaptor cap when not in use...

Страница 16: ...display LCD optional 3600 air out grille Flat plane design Sliver spray 8 meters remote controller Turbo cooling function Flexible air exhaust Advanced shower system 24 hour on off Cooling Dry Fan on...

Страница 17: ...2 2 Working environment 10 C 50 C 8 2 3 The humidity of electric part working environment RH10 RH95 8 2 4 The electric storage working temperature 20 C 70 C 8 3 PCB working environment 8 3 1 Toleranc...

Страница 18: ...ect the indoor evaporator from freezing Compressor will restart again when the indoor evaporator temperature rises to 10 C See the below graph At the anti freezing control the pump 1 and pump 2 mainta...

Страница 19: ...arge of drain water out start to work drain the water to the auxiliary tank If the water level drops below WL1 the pump 2 stop and the outer fan motor maintain the low fan At the above 2 steps if the...

Страница 20: ...t the compressor will work 5 minutes at least for each start up If the TS changed during this period judge TS and TA at once the 5 minutes wait will be cancel 8 5 5 If shutdown unit at cooling mode th...

Страница 21: ...lay shows the ambient temperature at fan mode the temperature can not be adjusted 8 7 3 The fan speed can by changed at fan mode the auto fan mode function is same as the fan speed control on auto mod...

Страница 22: ...different between TA and TS 8 9 5 2 If the fan motor is at low speed and TA TS 1 C the fan motor turn to middle fan and continue running 1 minute at least 8 9 5 3 If the fan motor is at middle speed...

Страница 23: ...eplace compressor Terminal R and S no continuity Open winding replace compressor 9 1 2 Ground test Use an ohmmeter set on its highest scale Touch one lead to the compressor body clean point of contact...

Страница 24: ...efore attempting to test 3 Apply ohmmeter probes to terminals on overload wires There should be continuity through the overload 9 1 6 Terminal overload internal Some model compressors are equipped wit...

Страница 25: ...below pinch off on the suction side of the compressor Connect the line from the nitrogen tank to the suction process tube Drift dry nitrogen through the system and unsolder the more distant connectio...

Страница 26: ...essors The terminal markings are on the cover gasket Use your wiring diagram to insure correct connections 9 2 6 Refrigerant charge The refrigerant charge is extremely critical It must be measured cha...

Страница 27: ...is marked with a red dot and is wired to the line side of the circuit 9 4 1 Capacitor test Remove capacitor from unit Check for visual damage such as bulges cracks or leaks For dual rated apply an ohm...

Страница 28: ...5 2 39 8239 25 10 52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58...

Страница 29: ...Refrigerant The amount of the refrigerant is too much making the compressor load too big Recycle and recharge the refrigerant after checking for the reason Compressor The compressor is blocked inside...

Страница 30: ...arefully rearrange tubing not to contact cabinet compressor shroud and barrier Water full alarm Water tank full Check and pour if the water tank is full Water depth sensor if failure Check and replace...

Страница 31: ...the terminals Repair and correct if loose Temperature setting Check and adjust the temperature setting Mode setting Check and adjust the mode setting Compressor Check and replace if the compressor the...

Страница 32: ...Exploded view spare part 30 12 Exploded view spare part 12 1 Exploded view of unit...

Страница 33: ...Exploded view spare part 31 12 2 Exploded view of accessory part...

Страница 34: ...0155 2 7 Pump 1 1 2240060019 2 8 Pump 2 1 2240060020 2 9 Pump fix plane 1 2122549022 2 10 Comp base pan 1 2122549017 2 11 Rubber 1 2272509015 2 12 Pump 1 drainage tube 1 2112549078 2 13 Pump 2 drainag...

Страница 35: ...Assembly 1 2152539004 31 Fan motor Inner 1 2240042252 32 Compressor 1 2140062230 33 Cond Assembly 1 2152539006 34 Air outlet assembly 1 2112549118 34 1 Step motor 1 2240020039 35 Front plane assembly...

Отзывы: