DIP Switches Configurations
No.
UP (ON)
DOWN (OFF)
Remarks
S1
Electric heat only
Electric heat and pump heat For heat pump unit only.
S2
Temperature Display in °C
Temperature Display in °F
S3
Wall thermostat enable
Control panel enable
S4*S5
UP*UP: 61°F – 86°F
UP*DOWN: 65°F – 78°F
DOWN*UP: 63°F – 80°F
DOWN*DOWN: 68°F – 75°F
Two configurations
(S4*S5) combine to
select set point range.
S6
Fan continuous run for heating
Fan cycle for heating
S7
Fan continuous run for cooling
Fan cycle for cooling
S8
Low temp. protection enable
Low temp. protection disable
S9
Use some types of wall
thermostat
Use PTAC other wall
thermostat
Consult with the sales
agency or manufacturer
for details.
NOTE: On heating mode, the temperature setting can’t be higher than 84°F.
•
Electric Heat Only (for heat pump unit only):
This setting is typically used for emergency
heating.
•
Wall Thermostat Enable:
A wired wall thermostat can be connected to the unit. To connect a
wall thermostat to the unit, this DIP switch must be moved to the Wall Thermostat Enable position
in order for the wall thermostat to function.
•
Set-point Temperature Limits:
Provides a restricted range of temperature control.
•
Heat and Cool Fan CON/CYC DIP switches:
Allows the fan to operate in continuous or cycle
mode while the unit is in heating or cooling mode.
o
Continuous (CON):
Allows fan to run continuously, circulating air even when the temperature
setting has been satisfied. This switch helps to maintain the ambient temperature closer to the
thermostat setting.
o
Cycle (CYC):
This setting allows the fan to cycle on and off with the compressor or electric
heater. The fan stops a short time after the set point is reached.
Functions for Front desk switch panel and Wire Controller
•
Front desk switch panel: If an ON/OFF switch is connected to the ports, the A/C unit can be
turned off with it. The LED display on the unit will show FC.
•
Wired controller: The LED display will show LC (reserved) if a wired controller is connected. If the
communication portal is one way, the buttons on the control panel will be invalid.
Note: This wired controller is optional, and it is connected to the switchboard.
Содержание MP12HMB63
Страница 1: ...SERVICE MANUAL PTACSERIES 7 000 15 000 BTU H ...
Страница 6: ...www mideaaircon com 4 3 Unit Components Decomposition Figure ...
Страница 7: ...www mideaaircon com 5 4 Installation Details 4 1 How to Install Unit ...
Страница 15: ...www mideaaircon com 13 5 Connect the wireless or wired module with controller Use the table below as guidance ...
Страница 31: ...www mideaaircon com 29 T5 T T4 T3 T2 T1 ...