Troubleshooting
TS03: Zero crossing detection error diagnosis and solution
Description
: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time
interval is abnormal.
Recommended parts to prepare:
• Connection wires
• Indoor main PCB
Troubleshooting and repair:
Check the connections and
power supply.
Correct the connections. Turn on the
unit when the power supply is good.
NO
Indoor main PCB is defective. Replace
indoor main PCB.
YES
Is it normal?
Note: Zero crossing detection error is only valid for the unit with AC fan motor, for other models, this error is
invalid.
Содержание MOAB30-09HFN8-QRD0GW
Страница 1: ...BLANC INVERTER SERIES SM_MA GA _R32_INV_EU_NA_1909 SERVICE MANUAL ...
Страница 2: ......
Страница 5: ......
Страница 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions ...
Страница 12: ...Contents 1 Model Reference 2 2 Pipe Length and Drop Height 3 3 Electrical Wiring Diagrams 4 Specifications ...
Страница 18: ...Outdoor unit wiring diagram 16022000019533 ...
Страница 20: ...Outdoor unit printed circuit board diagram 17122000040049 ...
Страница 22: ...Outdoor unit printed circuit board diagram 17122000023675 ...
Страница 24: ...Outdoor unit printed circuit board diagram 17122000036588 ...
Страница 59: ... Outdoor Unit Disassembly 3 2 Dimension 1 Panel Plate AA01 ...
Страница 60: ... Outdoor Unit Disassembly 4 2 Panel Plate AB01 ...
Страница 61: ... Outdoor Unit Disassembly 5 3 Panel Plate BA01 ...
Страница 62: ... Outdoor Unit Disassembly 6 For US models ...
Страница 63: ... Outdoor Unit Disassembly 7 4 Panel Plate B01 ...
Страница 64: ... Outdoor Unit Disassembly 8 For US models ...
Страница 65: ... Outdoor Unit Disassembly 9 5 Panel Plate CA01 ...
Страница 66: ... Outdoor Unit Disassembly 10 For US models ...
Страница 67: ... Outdoor Unit Disassembly 11 6 Panel Plate D01 ...
Страница 68: ... Outdoor Unit Disassembly 12 For US models ...
Страница 69: ... Outdoor Unit Disassembly 13 7 Panel Plate X101 ...