MCAC-KTSM-2007-2 Install The Drain Pipe
The Installation of MKB 159
Chart 26
St ow
Body
Drain pipe
Drain plug
Mater pan
Water re ceiver
Stow tube
Turn on the power, and operate the air conditioner under the "COOLING" mode. Listen to the sound of the
drain pump. Check whether the water is discharged well (a lag of 1min is allowed
before discharging,
according to the length of the drain pipe), and check whether water leaks
from the joints.
Cautions
: If there is any malfunction, please resolve it immediately.
Stop the air conditioner for there minutes, check if everything is ok. If the drain hose is located unreasonable,
water overflow will cause the Alarm indicator lamp flashing (For both cooling and heating type or cooling only
type), even the water leak out from the water receiver.
Check the drain pump whether drain water immediately when alarm sound for the high water lever. If the
water lever can't come down below to the limited water lever, the air conditioner will stop. Restart it until turn
off the power and drain off all the water.
Turn off the power, drain the water away.
The drain plug is used to empty the water-receiver for maintenance of the air conditioner. Please stuff it
imposition at all times during operation to avoid leakage.