Capacity Tables MCAC-KTSM-2007-2
16 Four Way Cassette Type
Cooling Capacity Table
Unit: W
Model
Water
inlet
temp.
(℃)
Water
FV
(LPM)
Water
PD
(kPa)
Air inlet condition
DB24
℃
DB25
℃
DB26
℃
DB27
℃
DB28
℃
WB17
℃
WB18
℃
WB19
℃
WB19.5
℃
WB21
℃
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
MKA-750
5
15
11.9
4001
4838
4121
5316
4241
5811
4455
6058
4472
6839
20
21.2
4217
5372
4368
5907
4504
6465
4727
6752
4774
7636
25
33.1
4392
5779
4551
6369
4711
6975
4942
7285
5006
8250
30
47.7
4504
6034
4679
6656
4847
7294
5078
7772
5166
8640
6
15
11.9
3834
4455
3962
4934
4081
5421
4296
5676
4313
6448
20
21.2
4041
4950
4185
5492
4328
6042
4551
6448
4592
7206
25
33.1
4193
5333
4360
5922
4519
6520
4742
6831
4815
7787
30
47.7
4296
5580
4472
6193
4639
6831
4879
7158
4958
8162
7
15
11.9
3675
4073
3802
4551
3921
5038
4137
5284
4153
6050
20
21.2
3858
4536
4001
5309
4145
5779
4368
6385
4416
6767
25
33.1
4001
4886
4161
5548
4320
6146
4551
6433
4624
7326
30
47.7
4097
5110
4264
5723
4440
6353
4671
6679
4759
7684
8
15
11.9
3507
3690
3643
4161
3762
4639
3977
4886
4001
5644
20
21.2
3675
4105
3826
4639
3970
5181
4193
5539
4241
6321
25
33.1
3810
4432
3970
5006
4129
5603
4360
5907
4432
6847
30
47.7
3890
4639
4065
5245
4232
5875
4472
6193
4560
7189
9
15
11.9
3356
3356
3484
3762
3611
4241
3826
4487
3842
5237
20
21.2
3499
3675
3651
4200
3794
4742
4017
5022
4073
5875
25
33.1
3611
3970
3778
4543
3938
5134
4169
5436
4249
6369
30
47.7
3690
4161
3866
4759
4033
5380
4273
5699
4360
6688
10
15
11.9
3197
3197
3324
3364
3452
3842
3666
4081
3690
4830
20
21.2
3324
3324
3475
3762
3619
4296
3842
4568
3898
5421
25
33.1
3428
3499
3587
4065
3754
4655
3985
4950
4065
5882
30
47.7
3491
3666
3666
4264
3834
4886
4073
5197
4169
6177
Remark
:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)