MCAC-TSM-2008-02
Hydraulic Connection
Installation
69
close to plate heat exchanger. Provided the pump installed outside of unit, the pump shall be connected at
water pipe’s outlet. The pump can be easily installed on the unit by removing the pump connection pipe.
Important
1) The chillers must be provided with a filling/top-up system connected to the return line and a drain cock
in the lowest part of the installation. Installations containing anti-freeze or covered by specific legislation
must be fitted with hydraulic disconnections.
2) The manufacturer is not liable for obstruction, breakage or noise resulting from the failure to install filters
or vibration dampers. Particular types of water used for filling or topping up must be treated with
appropriate treatment systems. For reference values, see the table.
PH 6-8
Electrical conductivity
less than 200 mV/cm (25
°
C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 50 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 50 ppm
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm
Filling the installation
-
Before filling, check that the installation drain cock is closed.
-
Open all installation and terminal air vents.
-
Open the gate valves.
-
Begin filling, slowly opening the water filling cock outside the unit
-
When water begins to leak out of the terminal air vent valves, close them and continue filling until the
pressure gauge indicates a pressure of 1.5 bars.
Emptying the installation
-
Before emptying, place the mains switch in the
“
off
”
position
-
Make sure the installation fill/top-up water cock is closed
-
Open the drain cock outside the unit and all the installation and terminal air vent valves.
Содержание MGC-F05W/N1
Страница 2: ......
Страница 14: ...Specification MCAC TSM 2008 02 12 Installation 2 Dimensions unit mm 2 1 MGC F05W N1 MGC F07W N1...
Страница 15: ...MCAC TSM 2008 02 Outdoor units Outdoor units 13 2 2 MGC F09W N1 MGC F10W N1 MGC F10W SN1...
Страница 16: ...Specification MCAC TSM 2008 02 14 Installation 2 3 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Страница 19: ...MCAC TSM 2008 02 Outdoor units Outdoor units 17 5 Wiring Diagrams 5 1 MGC F05W N1 MGC F07W N1...
Страница 20: ...Specification MCAC TSM 2008 02 18 Installation 5 2 MGC F09W N1 MGC F10W N1...
Страница 21: ...MCAC TSM 2008 02 Outdoor units Outdoor units 19 5 3 MGC F10W SN1 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Страница 39: ...MCAC TSM 2008 02 Outdoor units Outdoor units 37 8 Operation Limits...
Страница 42: ...Specification MCAC TSM 2008 02 40 Installation 10 Exploded View 10 1 MGC F05W N1...
Страница 44: ...Specification MCAC TSM 2008 02 42 Installation 10 2 MGC F07W N1...
Страница 46: ...Specification MCAC TSM 2008 02 44 Installation 10 3 MGC F09W N1 MGC F10W N1...
Страница 48: ...Specification MCAC TSM 2008 02 46 Installation 10 4 MGC F10W SN1...
Страница 50: ...Specification MCAC TSM 2008 02 48 Installation 10 5 MGC F12W SN1 MGC F16W SN1...
Страница 52: ...Specification MCAC TSM 2008 02 50 Installation 10 6 MGC F14W SN1...
Страница 81: ...MCAC TSM 2008 02 Running and Maintenance Installation 79 Part 4 Controller 1 Standard Controller 80...
Страница 86: ...Standard Controller MCAC TSM 2008 02 84 Controller 3 Select the Clock CL...
Страница 89: ...MCAC TSM 2008 02 Standard Controller Controller 87...
Страница 94: ...Standard Controller MCAC TSM 2008 02 92 Controller...