MCAC-UTSM-201501 Midea R410A T3 Top-discharge Split Type Series 50Hz
86
the ceiling with slab, ceiling which is in the same environment as the outdoor air. It is necessary to
apply 10mm or thicker adiabatic wool (16~20kg/m
2
) to the refrigerant pipe and the drain pipe in
addition to applying the general heat insulation materials. Enough heat insulation materials should
also be applied to the refrigerant joint and the pipe joint.
Note: the heat insulation of drain pipe refer to the installation of indoor unit.
Please use heat-resistant materials as heat insulation material of the air-side pipe. (e.g., EPT)
Cover heat insulation materials separately at the liquid side and the air side. Moreover, perform
heat insulation thoroughly for the air-side pipes of the indoor unit, and prevent water from
dripping outside the unit.
After applying the auxiliary heat insulation materials, use vinyl resin tape to seal refrigerant pipe
and drainage pipe to prevent water leak.
7. Electric Connection
7.1 Caution
Use special power supply for the air conditioner. Design power supplies specific to the indoor
unit and outdoor unit. The supply voltage must comply with the nominal voltage.
The external supply circuit of the air conditioner must have a ground wire, and the power supply
ground wire of the indoor unit must be connected with the external ground wire firmly.
The wiring must be performed by professional technicians according to the circuit diagram
labels.
Distribute the wires according to the relevant electric technical standards promulgated by the
State, and set the Residual Current-operated Circuit Breaker (RCCB) properly.
The power wire and the signal wire shall be laid out neatly and properly, without mutual
interference or contacting the connection pipe or valve.
No power cable is attached to this equipment. The user can select the power cable by reference
to the stipulated power supply specifications. No joint of wires is allowed.
Содержание MFA-76C(H)RN1
Страница 17: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 16 Pipe side view 4 Service Space Top view...
Страница 21: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 20 MTA 120CRN1 MTA 150CRN1...
Страница 35: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 34 MTA 120C H RN1 MTA 150CRN1...
Страница 36: ...Midea R410A T3 Top discharge Split Type Series 50Hz MCAC UTSM 201501 35 MHB 76C H RN1 MHB 96C H RN1...
Страница 44: ...Midea R410A T3 Top discharge Split Type Series 50Hz MCAC UTSM 201501 43 3 Dimensions 4 Service Space...
Страница 46: ...Midea R410A T3 Top discharge Split Type Series 50Hz MCAC UTSM 201501 45 6 Wiring Diagrams MFA 76HRN1 MFA 96HRN1...
Страница 47: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 46 MFA 76CRN1 MFA 96CRN1 MFAT 120CRN1...
Страница 109: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 108 E0 E1 E2 P1...
Страница 113: ...MCAC UTSM 201501 Midea R410A T3 Top discharge Split Type Series 50Hz 112 System low pressure protection...
Страница 154: ...Midea R410A T3 Top discharge Split Type Series 50Hz MCAC UTSM 201501 153 3 The wire connection...