Troubleshooting 93
7.16 P8: Typhoon protection (for all models)
LED
displays
P8
Typhoon protection
YES
Belongs to normal protection
When air conditioner is standby or in malfunction
stopping status, check if there is strong air blows the fan
phenomenon.
NO
Check whether the fan motor is normal.
YES
Replace outdoor main PCB or transfer board of the fan.
NO
Replace fan motor.