MCAC-VTSM-2014-09
R410A All DC Inverter Mini VRF
Specifications & Performance 39
MDV-V140W/DVN1
Cooling
Combination
(%)
(Capacity
index)
Outdoor
temperature
(°F DB)
Indoor temperature(°F DB/WB)
DB:69.4,WB:57.2
DB:73.9,WB:60.8
DB:78.4,WB:64.4
DB:80.6,WB:66.2
DB:82.7,WB:68
DB:87.3,WB:71.6
DB:89.6,WB:75.2
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
23
4.73
0.77
5.65
0.89
6.55
1.02
7
1.07
7.45
1.13
8.35
1.28
9.3
1.38
28.4
4.73
0.77
5.65
0.91
6.55
1.03
7
1.08
7.45
1.15
8.35
1.3
9.3
1.4
32
4.73
0.79
5.65
0.92
6.55
1.05
7
1.1
7.45
1.16
8.35
1.32
9.3
1.42
35.6
4.73
0.8
5.65
0.93
6.55
1.07
7
1.11
7.45
1.18
8.35
1.32
9.3
1.45
39.2
4.73
0.8
5.65
0.95
6.55
1.08
7
1.13
7.45
1.2
8.35
1.36
9.3
1.49
42.8
4.73
0.82
5.65
0.96
6.55
1.09
7
1.15
7.45
1.23
8.35
1.38
9.3
1.53
46.4
4.73
0.84
5.65
0.98
6.55
1.11
7
1.18
7.45
1.24
8.35
1.4
9.3
1.58
50
4.73
0.86
5.65
0.99
6.55
1.13
7
1.2
7.45
1.28
8.35
1.44
9.3
1.6
53.6
4.73
0.86
5.65
1
6.55
1.15
7
1.22
7.45
1.3
8.35
1.46
9.3
1.63
57.2
4.73
0.88
5.65
1.02
6.55
1.16
7
1.25
7.45
1.32
8.35
1.49
9.3
1.66
60.8
4.73
0.89
5.65
1.03
6.55
1.18
7
1.26
7.45
1.34
8.35
1.51
9.3
1.69
64.4
4.73
0.9
5.65
1.05
6.55
1.2
7
1.28
7.45
1.37
8.35
1.54
9.3
1.72
68
4.73
0.91
5.65
1.06
6.55
1.22
7
1.3
7.45
1.39
8.35
1.56
9.3
1.75
69.8
4.73
0.92
5.65
1.07
6.55
1.23
7
1.32
7.45
1.41
8.35
1.58
9.3
1.77
73.4
4.73
0.93
5.65
1.09
6.55
1.25
7
1.34
7.45
1.43
8.35
1.61
9.3
1.81
77
4.73
0.95
5.65
1.11
6.55
1.28
7
1.37
7.45
1.48
8.35
1.69
9.3
1.93
80.6
4.73
0.96
5.65
1.15
6.55
1.35
7
1.46
7.45
1.56
8.35
1.8
9.3
2.06
84.2
4.73
1.02
5.65
1.21
6.55
1.43
7
1.55
7.45
1.67
8.35
1.92
9.3
2.19
87.8
4.73
1.07
5.65
1.28
6.55
1.51
7
1.64
7.45
1.77
8.35
2.04
9.3
2.33
91.4
4.73
1.14
5.65
1.36
6.55
1.61
7
1.74
7.45
1.88
8.35
2.17
9.3
2.48
95
4.73
1.2
5.65
1.44
6.55
1.7
7
1.84
7.45
1.99
8.35
2.3
9.3
2.63
98.6
4.73
1.26
5.65
1.52
6.55
1.8
7
1.95
7.45
2.11
8.35
2.44
9.3
2.8
102.2
4.73
1.33
5.65
1.6
6.55
1.9
7
2.06
7.45
2.24
8.35
2.59
9.3
2.97
105.8
4.73
1.39
5.65
1.67
6.55
1.97
7
2.16
7.45
2.33
8.35
2.72
9.3
3.11
109.4
4.73
1.48
5.65
1.79
6.55
2.04
7
2.26
7.45
2.39
8.35
2.86
9.3
3.25
Note:
1
.
is tested under our standard condition.
2.Avoid to run the unit when the temperature is above 109.4
℉
(43
℃
).
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.