MCAC-VTSM-2016-02 R410A All DC Inverter Mini VRF
Troubleshooting 65
Press the button for 5 seconds:
If the
“running” and “warning” lights are normally on, that means the address code is 9=(8
+
1)
If the lights are blink, the address code should plus 16, so the address code is 25=16
+
(8
+
1)
Press the button for 10 seconds:
If the
“timer” and “warning” lights are normally on, that means the capacity code is 5=(4
+
1) and the
capacity of indoor unit is 71×100W(2.5HP).
2. If the signal is weak, connect
a 120Ω resistor between P and Q of the farthest indoor unit, or connect a
0.5-1.5uF capacitor between P and Q of outdoor unit. Installation refers to the following picture:
Note:
Communication wires should be shield wire and indoor units should be connected in series.
Indoor Unit
Outdoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
R=
120Ω
Capacitor