R410A All DC Inverter Mini VRF
MCAC-VTSM-2016-02
56 Installation
6. Outdoor Unit Wiring
The Specification of Power
Table 6-1
Capacity
120 model
140 model
160 model
Outdoor Unit power
Phase
1 phase
1 phase
1 phase
Voltage and
Frequency
220-240V~50Hz & 208-230V~60Hz
Power
Wiring(mm
2
)
Wire size must comply with local codes
Fuse (A)
60
60
60
Indoor unit/Outdoor unit Signal wire
(Weak electric signal) (mm
2
)
3-core shielded wire
3X0.75
CAUTION
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring
according to the National Wiring Regulation.
Caution:
●
Employ an electrical engineer for wiring.
●
Complete wiring according to national electrical standards.
●
To reduce interference, use a three-core shielded twisted pair as the outdoor unit signal cable. Do not use a multi-core cable.
●
Incorporate the outdoor unit and indoor unit connection wiring system and refrigerant pipe system for the same system.
●
The power supply, electric leakage protectors, and manual switches of the indoor units that connect to the same outdoor unit
must be universal. Use the same loop for the indoor unit power. Connect to the same outdoor unit must be universal. Use the
same loop for the indoor unit power supplies in the same system. Power on/off at the same time.
●
If the power supply uses a branch loop, install an electricity leakage protector and a manual switch.
●
Design a dedicated power supply for the indoor unit and outdoor unit.
Indoor/Outdoor Unit Signal Wire
Connect the wire according to their numbers.
Wrong connection may cause malfunction.
Wiring Connection
Seal the wiring connection with the insulation material, or the condensing dew will be caused.
NOTE
The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system.